Manual

Single-axis controllers
Mechanical installation
Important notes
4
92
EDS94SPP101 EN 7.1
4.5 Mechanical installation
4.5.1 Important notes
Note!
The devices must be installed in housings (e.g. control c abinets) to meet
applicable regulations.
4.5.2 Devices in the range 2 ... 24 A (0.37 ... 11 kW)
Proceed as follows for the installation:
1. Prepare M5 threaded holes on the mounting plate according to the mounting grid.
2. When using footprint filters: Screw installation backplane and footprint filter
together.
Use screw and washer assemblies M5 x 20 mm or hexagon socket screws
M5 x 20 mm with washers.
Tightening torque: 3.4 Nm (30 lb-in)
3. Screw the installation backplane or footprint filter with installation backplane onto
the mounting plate. Do not yet tighten the screws.
Use M5 screw and washer assemblies or M5 hexagon socket screws with washers.
The screw joint in the installation backplane may jut out no more than 7 mm.
4. Repeat steps 2 and 3 with further installation backplanes which are mounted side by
side.
5. Align all installation backplanes.
6. Screw all installation backplanes/footprint filters onto the mounting plate.
Tightening torque: 3.4 Nm (30 lb-in).