L−force Controls Ä.J41ä LDCDP−EPC50ACU .
, Please read these instructions before you start working! Follow the enclosed safety instructions.
Validity information These instructions are valid for ƒ ACU UPS software for Lenze Industrial PCs Trademark Windows XPâ, Windows XPâ Embedded and Windowsâ Embedded Standard 2009 are registered trademarks or trademarks of Microsoft Corporation in the USA and/or other countries. Any additional trade names given in this documentation are trademarks of their corresponding owners. Document history Material number Version Description 13218873 1.0 11/2007 TD29 First edition 13303164 2.
i 1 2 3 4 Contents Software Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.3 Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software description 1 Operating mode 1 Software Description The industrial PC option "ACU UPS Control Unit" in combination with a battery/capacitor pack extends the industrial PC (IPC) by one UPS function.The ACU UPS software controls the behaviour of the IPC in this process as soon as the hardware identifies a supply voltage failure. The ACU UPS control unit is a factory set pre−equipment if you chose this option when placing your purchase order.
1 Software description Messages Message in case of a voltage failure 1.3 Messages 1.3.1 Message in case of a voltage failure In the case of a voltage failure, the ACU UPS takes charge of the IPC supply. The remaining time to the IPC shutdown is displayed on the desktop. (¶ 14). EPC50ACU−003 Fig. 1−1 1.3.2 Desktop message in the event of a voltage failure Message after a change in ACU UPS state Changes in ACU UPS state are indicated by a change in colour of the ACU symbol on the Windows task bar.
Software operation 2 Start and Close Software 2 Software Operation 2.1 Start and Close Software Start After the IPC has been booted, the software starts automatically and then runs in the background. A symbol pops up in the information bar. EPC50ACU−001 Fig. 2−1 ) Windows task bar with ACU UPS symbol Note! If an L−force Controller is delivered with ACU UPS but without a battery pack, the ACU UPS software is installed but UPS support is deactivated.
2 Software operation Start and Close Software Close Usually, the software is automatically closed by Windows. If you want to close the software manually, right−click the ACU symbol in the information bar of the Windows task bar and select Exit from the context menu. EPC50ACU−002 Fig. 2−3 Windows task bar with opened context menu ACU UPS V2.x: UPS functionality is switched off until it is switched on again via the context menu. ACU UPS V3.x/V4.
Software operation 2 Open User Interface 2.2 Open User Interface ) Note! For configuring the ACU software, administrator rights are required. Otherwise, only actual states can be displayed. ƒ If you want to View ACU UPS Configuration, double−click the ACU symbol in the information bar of the Windows task bar. The ACU software dialog is displayed. The registries of this dialog show the ACU UPS software settings. Various settings which affect software only can be made (e.g.
2 Software operation User Interface Dialogs Registry "ACU State" − Show UPS State 2.3 User Interface Dialogs 2.3.1 Registry "ACU State" − Show UPS State ACU USV V2.x: Dialog Box Type Value Range − Explanation Hardware Type Power OK/Fail Input Voltage State; OK or Failure UPS On/Off On: UPS functionality activated Buffer Time [s] Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out.
Software operation 2 User Interface Dialogs Registry "ACU State" − Show UPS State ACU USV V3.x/V4.x: Dialog Box Type Value Range − Power UPS Explanation Hardware Type OK/Fail Input Voltage State; OK or Failure On/Off On: UPS functionality activated Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out. Buffer Time 4 min.
2 Software operation User Interface Dialogs Registry "ACU Control" − Configure UPS 2.3.2 Registry "ACU Control" − Configure UPS ) Note! This registry is only shown when the ACU software has been called up via the system panel. It is not shown when the software is called up by double−clicking the symbol in the information bar of the Windows task bar. ACU USV V2.x: Dialog Box Buffer Time [s] Delay Time 12 Value Range Explanation 0.00 ... 64.
Software operation 2 User Interface Dialogs Registry "ACU Control" − Configure UPS ACU USV V3.x: Dialog Box Value Range Explanation Delay Time [s] 0.00 ... 64.00 s Period of time to wait until a voltage failure is reported by the ACU UPS control unit. Thus, voltage fluctuations are filtered out. Buffer Time 4 min.; infinite Maximum period of time the industrial PC can be fed by the battery/capacitor pack, depending on the hardware.
2 Software operation User Interface Dialogs Registry "Time Set" − Time Before Shutdown 2.3.3 Registry "Time Set" − Time Before Shutdown ACU UPS Vx.x: Dialog Box Time Before Shutdown 2.3.4 Value Range 0 ... 60 s Explanation Period of time from identifying a mains failure by the ACU UPS control unit until shutting down the IPC. This period of time must be shorter than the delay time (^ 12) plus the period of time needed by the IPC to shut down.
Software operation 2 User Interface Dialogs Registry "Shutdown" − Force Shutdown 2.3.5 Registry "Shutdown" − Force Shutdown ACU UPS Vx.x: Dialog Box Value Range Explanation Shutdown On/Off Default Setting Force Shutdown On/Off If you are using the default setting and an application prompts you to make a user entry when shutting down the PC, the PC cannot be shut down automatically.
2 Software operation User Interface Dialogs Registry "LogFile" − View Program Messages 2.3.6 Registry "LogFile" − View Program Messages ACU UPS Vx.x: All ACU software messages are recorded in the ACU.log file and can be viewed there. Dialog Box Value Range Explanation [Position Log File] − Select the folder the ACU.log file shall be written to. [Show Log File] − Display ACU.log File ) Note! The log file data is moved to the "ACU.
Software installation 3 3 Software Installation The ACU UPS control unit software is a factory set pre−equipment if you chose this option when placing your purchase order and if you obtained the operating system via a Lenze storage medium. In other cases, start the setup program on the program CD and follow the instructions of the setup assistent. ) Note! After the ACU UPS software has been reinstalled, UPS functionality is deactivated for versions V3.x/V4x and activated for version V2.x.
Q © 06/2012 F Lenze Automation GmbH Hans−Lenze−Str. 1 D−31855 Aerzen Germany Service Lenze Service GmbH Breslauer Straße 3 D−32699 Extertal Germany ( Ê ü +49 (0)51 54 / 82−0 ( Ê 00 80 00 / 24 4 68 77 (24 h helpline) +49 (0)51 54 / 82 − 28 00 Lenze@Lenze.de +49 (0)51 54 / 82−11 12 Service@Lenze.de www.Lenze.com LDCDP−EPC50ACU § .J41 § EN § 4.