Manual
6 Electrical installation
Assignment of the terminals
EDK82ZAFPC-201 DE/EN/FR 6.0
64
H2_BelegungAnschlKlemmen-INS_Klembesch
Assignment of the terminals
Terminal
X3.1/
Designation Function / level
E1
Digital inputs *) Adapt the individual setting via C0007 or C0410.
Input resistance: 3.3 k
Ω
0 = LOW (0 ... +3 V DC) PLC level, HTL
1 = HIGH (+12 ... +30 V DC) PLC level, HTL
(reference: GND2)
E2
20 DC voltage source for the internal supply of the digital inputs E1 and
E2
+20 V DC (reference: GND1)
I
max
= 20 mA
39 GND2 Reference potential of the
digital inputs at X3.1/E1 and X3.1/E2
controller inhibit (CINH) at X3.2/28
59 External DC voltage supply for the function module
+24 V DC
±
10% (reference: GND1)
Current consumption on 24 V DC: 80 mA
The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.
7 GND1 Reference potential for X3.1/20 and X3.2/20
*) Alternatively frequency input 0 ... 10 kHz (one-track) or 0 ... 1 kHz (two-track) configuration via C0425