Owner manual
Diagnostics
LED status displays
9
l 85
EDS82ZAFPC201 EN 4.0
9 Diagnostics
9.1 LED status displays
E82ZAFP020B
LED
Description
Pos. Colour Condition
0 Yellow
Off No communication with the PROFIBUS master.
Blinking Communication with the PROFIBUS master has been established via the
function module.
1 Green
Off l The function module is not supplied with voltage.
l The standard device and/or the external voltage supply is/are switched
off.
Blinking
(const.)
The function module is supplied with voltage but has not established a
connection to the standard device.
Causes:
l The standard device is switched off.
l The standard device is in the initialisation phase.
l The standard device is not available.
Blinking
(3x short)
Internal error of the function module
On The function module is supplied with voltage and has established a
connection to the standard device.