Owner manual
Codes
Communication−relevant Lenze codes
10
l
92
EDS82ZAFPC201 EN 4.0
C1510: Configuration of process input data
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1510 23065
d
=
5A19
h
FIX32
1 (PIW1) 18
See table below
2 (PIW2) 3
3 (PIW3) 4
4 (PIW4) 5
5 (PIW5) 6
6 (PIW6) 7
7 (PIW7) 8
8 (PIW8) 9
9 (PIW9) 10
10 (PIW10) 11
The assignment of the bit status information or the actual controller values to the up to 10
process data input words (PIW) of the master can be freely configured.
Selection Scaling
1 FIF status word 1 (FIF−STAT1) 16 bits
2 FIF status word 2 (FIF−STAT2) 16 bits
3 Output frequency with slip (MCTRL1−NOUT+SLIP) ±24000 º ±480 Hz
4 Output frequency without slip (MCTRL1−NOUT) ±24000 º ±480 Hz
5 Apparent motor current (MCTRL1−IMOT) 2
14
º100 % rated device current
6 Actual process controller value (PCTRL1−ACT) ±24000 º ±480 Hz
7 Process controller setpoint (PCTRL1−SET) ±24000 º ±480 Hz
8 Process controller output (PCTRL1−OUT) ±24000 º ±480 Hz
9 Controller load (MCTRL1−MOUT) ±2
14
º±100 % rated motor torque
10 DC−bus voltage (MCTRL1−DCVOLT) 16383 º 565 V DC for 400 V mains
16383 º 325 V DC for 230 V mains
11 Ramp function generator input (NSET1−RFG1−IN) ±24000 º ±480 Hz
12 Ramp function generator output (NSET1−NOUT) ±24000 º ±480 Hz
13 FIF−OUT.W1 16 bits or 0 ... 65535
14 FIF−OUT.W2 16 bits or 0 ... 65535
15 FIF−OUT.W3 0 ... 65535
16 FIF−OUT.W4 0 ... 65535
17 DRIVECOM control word (DRIVECOM−CTRL) 16 bits
18 DRIVECOM status word (DRIVECOM−STAT) 16 bits
19 PROFIdrive control word (PROFIdrive−CTRL) 16 bits
20 PROFIdrive status word (PROFIdrive−STAT) 16 bits