Owner manual

Codes
Monitoring codes
10
l
95
EDS82ZAFPC201 EN 4.0
10.3 Monitoring codes
C0126: Behaviour with communication error
Code Subcode Index
Possible settings
Data type
Lenze Selection
C0126 24449
(0x5F81)
10
0 [1] 10
FIX32
0: All monitoring functions deactivated.
2: Monitoring of internal communication
active
Monitoring of internal communication between function module and controller.
If the monitoring function is activated, a communication abort initiates TRIP (CE5).
, Documentation for the standard device
Please refer to this documentation for a complete description of the setting
options of this code.
C1513: Monitoring response time of PZD communication
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1513 23062
d
=
5A16
h
3000 0 [1 ms] 65535 FIX32
The value of the response monitoring time is provided by the master.
) Note!
A change in the monitoring time becomes effective immediately.
Monitoring starts with the receipt of the first telegram.
The setting C1513 = 0 deactivates the monitoring function.