Owner manual
Codes
Diagnostics codes
10
l
99
EDS82ZAFPC201 EN 4.0
C1521: Display of all words from master
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1521 23054
d
=
5A0E
h
g 0 [1] 65535 U16
1 (POW1)
...
10 (POW10)
Display of the master’s process data output words POW1 ... POW10 in the different
subcodes. All words are displayed. Only the configured words are valid.
The assignment of the up to 10 process data output words (POW) of the master to bit
control commands or controller setpoints can be freely configured via code C1511.
C1522: Display of all process data words to standard device
Code Subcode Index
Possible settings
Data type
Lenze Selection
C1522 23053
d
=
5A0D
h
g 0 [1] 65535 U16
1
...
16
Display of the process data words 1 ... 16 which are transferred from the function module
to the standard device:
Subcode Process data word
1 FIF control word 1 (FIF−CTRL1)
2 FIF control word 2 (FIF−CTRL2)
3 Setpoint 1 (NSET1−N1)
4 Setpoint 2 (NSET1−N2)
5 Additional setpoint (PCTRL1−NADD)
6 Actual process controller value (PCTRL1−ACT)
7 Process controller setpoint (PCTRL1−SET1)
8 Reserved
9 Torque setpoint or torque limit value (MCTRL1−MSET)
10 PWM voltage (MCTRL1−VOLT−ADD)
11 PWM angle (MCTRL1−PHI−ADD)
12 Reserved
13 FIF−IN.W1
14 FIF−IN.W2
15 FIF−IN.W3
16 FIF−IN.W4