User guide

Electrical installation
Bus cable length
6
EDK82ZAFUC010 DE/EN/FR 4.0
59
H2 BusLeitgsLaenge−Leitungslaenge_3
3. Compare the two values determined.
If the value given in Tab. 2 is smaller than the required total cable length from Tab. 1,
repeaters must be used. Repeaters divide the total cable length into segments.
Note!
ƒ Note the reduction of the total cable length due to the signal delay of the
repeater (see example
60).
ƒ Mixed operation
There is mixed operation if different nodes are connected to the same
mains.
If the total cable lengths of the nodes are different at the same baud
rate, the smaller value must be used to determine the max. cable
length.
Example: Selection help
Given:
l Cable cross−section:
0.5 mm
2
(according to cable specification 57)
l Number of nodes
connected:
100
l Repeater:
Lenze repeater, type 2176 (cable reduction: 30 m)
For the above selections the following cable lengths / number of repeaters must be
observed:
Baud rate [kbps] 10 20 50 125 250 500 1000
Max. cable length [m] 8000 3900 1500 630 290 120 25
Segment cable length [m] 270 270 270 270 290 120 25
Number of repeaters 33 16 6 2