Manual
Electrical installation
Wiring according to EMC
6
EDKMF2102 DE/EN/FR 7.1
61
H2_EMV_Verdraht−EMV
Wiring according to EMC
For wiring according to EMC requirements observe the following points:
Note!
ƒ Separate control/data cables from motor cables.
ƒ In case of digital signals, connect the shields of control/data cables on both
sides.
ƒ Use an equalizing conductor with a cross−section of at least 16mm
2
to
avoid potential differences between the bus nodes (reference:PE).
ƒ Observe the other notes concerning EMC−compliant wiring given in the
documentation for the standard device.