Manual

7 Commissioning
Commissioning for 8200 series standard devices
EDKMF2102 DE/EN/FR 7.1
76
inbetriebnahme82XXvector
Detailed
information
ProcedureStep
It is now possible to communicate with any controller, i.e. all codes can be read and all writable codes
can be changed.
4.
Make other necessary controller settings.
Commissioning of the controller
Documentation
for the respective
controller
l Select the frequency setpoint with C0046 and the control word
with C0135.
l Set the operating mode C0001= 3.
l With speed setpoint = 0, quick stop (QSP) is active in this
operating mode at switch−on. This prevents uncontrolled starting
of the controller.
Deactivation of the QSP function: Set C0135/bit 3 = 0 (FALSE).