7 Diagnostics & troubleshooting
7.5 Error messages
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
ID1: Motor data identification error During the identification of the motor
parameters, an error has occurred.
Possible causes:
Interrupted motor cable.
• Switched-off power section during the
identification.
• Implausible start parameter settings.
Check the motor connections and the
corresponding plug connector on the
device and, if necessary, the motor
terminal box.
Correct start parameters for the motor
parameter identification (motor
nameplate data).
Stable power supply of the device.
ID3: CINH motor data identification The device has detected controller inhibit
during the motor data identification.
• This cancels the identification process.
The Lenze setting of the motor data is
used.
Do not set controller inhibit during the
motor data identification.
Do not execute any device function
which may activate controller inhibit.
ID4: Resistor identification error The device has recognised that an error
has occurred in the calculation of the
motor cable resistance.
• The parameters for cable cross-section
and cable length are implausible.
Enter sensible values for cable cross-
section and motor cable length.
LP1: Motor phase failure Motor phase failure - power section
This error message is displayed if a
motor phase carries less current of one
half-wave than set in C00599.
Check the motor connections and the
corresponding plug connector on the
device and, if necessary, the motor
terminal box.
Check the trigger threshold (C00599).
LU: DC bus undervoltage The device has detected a DC bus
undervoltage. The inverter control is
switched off because the drive properties
of the motor control cannot be provided
anymore due to the DC bus undervoltage.
Depending on the configuration of the
auto-start lock function, C00142 serves
to set that, if this error has been
tripped, the controller only starts after
the controller inhibit is switched.
Switch on mains supply or ensure
sufficient supply via DC bus.
Adjust setting in C00142 if required.
MCI1: Module missing / incompatible The optional communication module has
been removed or there is a connection
problem or incompatibility with the
standard device.
Check connection between the
communication module and standard
device.
Check if the module is plugged in
correctly.
In case of an incompatibility, either the
module or the software of the standard
device is out of date. In this case, please
contact Lenze.
OC1: Power section - short circuit The device has recognised a short circuit of
the motor phases. To protect the device
electronics, the inverter control is
switched off.
• Mostly, incorrectly executed motor
connections are the cause.
• If the device is inappropriately
dimensioned with regard to the motor
load and the current limitation in the
controller (Imax controller) is set
incorrectly, this error message may also
occur.
Check motor connections and the
corresponding plug connector on the
device.
Only use permissible combinations of
device power and motor power.
Do not set the dynamics of the current
limitation controller too high.
Error message Cause Remedies