8 Adapting the application individually
8.2 Activating additional functions in the signal flow
58
Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.2 Activating additional functions in the signal flow
The following parameters serve to activate further functions in the main signal flow that are first
deactivated by default:
Parameter Name Info
Application parameters (extended)
C00598/1 Resp. to open circuit AIN1 Response to open circuit at the analog input when
being configured as 4 ... 20 mA current loop.
Lenze setting: "TroubleQuickStop". The drive is braked
to standstill within the deceleration time
parameterised for quick stop independently of the
defined setpoint and can be kept there.
C00950/1 Activation of signal interpolation Signal interpolation and monitoring
(see reference manual; FB L_Interpolator_1)
C00950/2 Activation of signal monitoring
C00951 L_Interpolator_1:
No. of interpolation steps
C00952 L_Interpolator_1:
Limit value - error cycles
C00696 L_OffsetGainP_1: Offset Offset and gain
(see reference manual; FB L_OffsetGainP_1)
C00670 L_OffsetGainP_1: Gain
C00635 L_NSet_1: nMaxLimit Speed limit values
( 59)
C00636 L_NSet_1: nMinLimit
C0632/1...3 L_NSet_1: Blocking speed 1 ... 3 max Speed blocking zones
( 60)
C0633/1...3 L_NSet_1: Blocking speed 1 ... 3 min
C00134 Ramp smoothing main setpoint Ramp smoothing
( 61)
C00182 S-ramp time PT1
C02830 DIx: Debounce time Debounce and delay times for digital inputs and
outputs
C00423 DOx: Delay times
C00472/3 LS_ParFree_a: Value 3 Torque limitation in motor mode and in generator
mode. Lenze setting: 100 %
• The drive cannot output a higher torque in
motor/generator mode than set here.
• If V/f characteristic control (VFCplus) is selected,
limitation is indirectly
performed via the Imax
controller.
C00472/4 LS_ParFree_a: Value 4