L-force Communication Ä.
L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Contents Contents 1 2 3 4 5 About this documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 1.1 Document history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.2 Conventions used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E84AYCIB communication manual (INTERBUS) Contents 6 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 6.1 Before initial switch-on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 6.2 Possible settings through DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.2.
E84AYCIB communication manual (INTERBUS) Contents 13 14 Parameter reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 13.1 Parameters of the communication module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 13.2 Table of attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Index . . . . . . . .
E84AYCIB communication manual (INTERBUS) About this documentation 1 About this documentation Contents The descriptions contained in this documentation refer only to the E84AYCIB communication module (INTERBUS). Note! This documentation supplements the mounting instructions supplied with the communication module and the "Inverter Drives 8400" hardware manual. The features and functions of the communication module are described in detail. Typical applications are illustrated by means of examples.
E84AYCIB communication manual (INTERBUS) About this documentation Target group This documentation addresses to people involved in configuring, installing, commissioning and maintaining a machine's networking and remote maintenance features. Tip! You will find documentation and software updates relating to Lenze products on the Internet, in the "Services & Downloads" area at: www.Lenze.
E84AYCIB communication manual (INTERBUS) About this documentation Document history 1.1 Document history Material number Version Description 13295951 1.0 06/2009 TD17 First edition 13320780 2.0 11/2009 TD17 Parameter descriptions updated. 13329723 3.0 02/2010 TD17 Chapters "Diagnostics" and "Installation" updated. 13362260 4.
E84AYCIB communication manual (INTERBUS) About this documentation Conventions used 1.2 Conventions used This documentation uses the following conventions to distinguish between different types of information: Type of information Identification Examples/notes Spelling of numbers Decimal Hexadecimal Binary • Nibble Decimal separator Standard notation 0x[0 ... 9, A ... F] In quotation marks Point Point Example:1234 Example: 0x60F4 Example: ’100’ Example: ’0110.0100’ The decimal point is always used.
E84AYCIB communication manual (INTERBUS) About this documentation Terminology used 1.3 Terminology used Term Meaning Standard device Lenze frequency inverter from the "Inverter Drives 8400" product series, with which the communication module can be used. Application as directed ( 14) Controller 10 »Engineer« Lenze software, supporting you during the entire life cycle of a machine - from the planning phase to maintenance.
E84AYCIB communication manual (INTERBUS) About this documentation Notes used 1.
E84AYCIB communication manual (INTERBUS) Safety instructions General safety instructions and application notes 2 Safety instructions Note! It is absolutely vital that the stated safety measures are implemented in order to prevent serious injury to persons and damage to material assets. Always keep this documentation to hand in the vicinity of the product during operation. 2.1 General safety instructions and application notes Lenze drive components ... – may only be used as directed.
E84AYCIB communication manual (INTERBUS) Safety instructions Device- and application-specific safety instructions 2.2 Device- and application-specific safety instructions During operation, the communication module must be securely connected to the standard device. Use a safely separated power supply unit in accordance with EN 61800-5-1 ("SELV"/ "PELV"). Only use cables that meet the listed specifications. Specification of the bus cable ( 30) 2.
E84AYCIB communication manual (INTERBUS) Product description Application as directed 3 Product description 3.1 Application as directed The communication module ... Is an accessory module that can be used in conjunction with the following standard devices: Product series Type designation Inverter Drives 8400 StateLine E84AVSCxxxxx From software version 04.00 Inverter Drives 8400 HighLine E84AVHCxxxxx 04.00 Inverter Drives 8400 TopLine E84AVTCxxxxx 01.
E84AYCIB communication manual (INTERBUS) Product description Product features 3.3 Product features Interface module for the INTERBUS communication system for attachment to the expansion slots of Inverter Drives 8400 The communication module can either be supplied internally by the 8400 standard device or externally by a separate voltage source.
E84AYCIB communication manual (INTERBUS) Product description Terminals and interfaces 3.4 Terminals and interfaces 2 connections for the INTERBUS – 1 input (9-pole Sub-D plug) – 1 output (9-pole Sub-D socket) 2-pole plug connector with spring connection for the external voltage supply of the communication module DIP switch for setting the ... – Number of process data words and parameter data words – Baud rate Front LEDs for diagnostics ...
E84AYCIB communication manual (INTERBUS) Technical data General data and operating conditions 4 Technical data 4.1 "Inverter Drives 8400" hardware manual This manual contains data on the ambient conditions and the electromagnetic compatibility (EMC) that also apply to the communication module.
E84AYCIB communication manual (INTERBUS) Technical data Protective insulation 4.2 Protective insulation Danger! Dangerous electrical voltage If Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage ≥ 400 V, external measures need to be implemented in order to provide reliable protection against accidental contact.
E84AYCIB communication manual (INTERBUS) Technical data Protective insulation The illustration below ... shows the arrangement of the terminal strips and the separate potential areas of the controller. serves to determine the decisive protective insulation between two terminals located in differently insulated separate potential areas. Note! The INTERBUS input (X206) is isolated from the voltage supply (X205) and the INTERBUS output (X207). Bus X101 X106 X206 Ext.
E84AYCIB communication manual (INTERBUS) Technical data Protective insulation Terminal strip Connection X100 Mains/DC-bus connection X101 Relay contact X105 Motor/brake resistor X106 Motor PTC X1 System bus (CANopen) X3 Analog inputs/outputs X4 Digital outputs X5 Digital inputs X6 Diagnostics MCI Slot for communication module MMI Slot for memory module Example Which type of protective insulation is used between the bus terminal of the device module in slot MCI and the mains terminal X100? The separate p
E84AYCIB communication manual (INTERBUS) Technical data Protocol data 4.3 4.4 Protocol data Field Values Process data words 0 ... 10 words (16 bits/word) Supported PMS services • • • • • • • • Initiate Abort Reject Read Write Get-OD Identify Status Communication time The communication time is the time between the start of a request and the arrival of the corresponding response. The communication times in the INTERBUS network depend on the...
E84AYCIB communication manual (INTERBUS) Technical data Dimensions 4.5 Dimensions E84YCIB0016 [4-2] Dimensions Type E84AYCIB 22 Dimensions [mm] a b c c1 67 50 57 8 L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Installation 5 Installation Stop! Electrostatic discharge Electronic components within the communication module can be damaged or destroyed by electrostatic discharge. Possible consequences: • The communication module is damaged. • Fieldbus communication is not possible or is faulty. Protective measures: • Ensure that you are free of electrostatic charge before you touch the module. EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Installation Mechanical installation 5.1 Mechanical installation The communication module can be plugged into the MCI slot or removed from there while the controller is switched on. When the module is plugged in, it is recognised automatically and checked for plausibility regarding its function and version. 5.1.1 Mounting for standard devices 0.25 kW and 0.37 kW E84YCPM002D [5-1] Mounting for standard devices 0.25 kW and 0.37 kW Mounting steps 1.
E84AYCIB communication manual (INTERBUS) Installation Mechanical installation 5.1.2 Mounting for standard devices from 0.55 kW onwards E84YCPM002A [5-2] Mounting for standard devices from 0.55 kW onwards Mounting steps 1. Slightly impress the pressure surface on the top side of the standard device MCI slot cover (1). 2. Bend the cover forward and remove it from the standard device (2). 3. Loosen the securing screw for the communication module at the standard device (3). 4.
E84AYCIB communication manual (INTERBUS) Installation Mechanical installation 5.1.3 Replacing the communication module E84YCPM002B [5-3] Replacing the communication module Mounting steps 1. Loosen the securing screw for the communication module at the standard device (1). 2. Remove the communication module from the MCI slot of the standard device (2). 3. Insert the new communication module into the MCI slot of the standard device (3). 4. Tighten the securing screw again (4). 26 L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Installation Electrical installation 5.2 Electrical installation 5.2.1 Documentation for the standard device, control system, plant/machine Observe the notes and wiring instructions contained in this documentation. EMC-compliant wiring In typical systems, standard shielding of the Ethernet cables is sufficient.
E84AYCIB communication manual (INTERBUS) Installation Electrical installation 5.2.3 INTERBUS connection The INTERBUS connection of the communication module is effected via X206 (input, 9-pole Sub-D plug) and X207 (output, 9-pole Sub-D socket). E84YCIB001E [5-5] INTERBUS terminals X206 (input) and X207 (output) The nodes on the bus system have to be connected to each other by means of a fieldbus cable in accordance with the INTERBUS specification.
E84AYCIB communication manual (INTERBUS) Installation Electrical installation Assignment of the 9-pole Sub-D plug X206 (IN) Pin Designation Input/output Description 1 DO1 Input RS485: DO1 not inverted 2 DI1 Output 3 GND 4 Free 5 Vcc5 Output 5 V DC 6 /DO1 Input RS485: DO1 inverted 7 /DI1 Output RS485: DI1 inverted 8 Vcc5 Output 5 V DC 9 Free RS485: DI1 not inverted Reference potential Not assigned Not assigned Assignment of the 9-pole Sub-D socket X207 (OUT) Pin Designati
E84AYCIB communication manual (INTERBUS) Installation Electrical installation 5.2.4 Specification of the bus cable Note! Only use cables that meet the listed specifications. Specification of the INTERBUS cable 5.2.5 Cable type Sold by the meter (e.g. PHOENIX CONTACT: IBS RBC meter-T, order no. 28 06 28 6) No. of conductors 3 x 2, twisted in pairs, with joint shielding Conductor cross-section > 0.
E84AYCIB communication manual (INTERBUS) Installation Electrical installation 5.2.6 External voltage supply The communication module can be supplied externally with voltage via separate supply cables at the 2-pole plug connector (X205). Note! With external voltage supply, always use a separate power supply unit, safely separated in accordance with EN 61800-5-1 in every control cabinet ("SELV" / "PELV").
E84AYCIB communication manual (INTERBUS) Installation Electrical installation Assignment of the X205 plug connector Designation Explanation + U = 24 V DC (21.6 V - 0 % … 26.4 V + 0 %) I = 180 mA - Reference potential for external voltage supply Terminal data Field Values Electrical connection 2-pole plug connector with spring connection Possible connections Rigid: 0.2 ... 1.5 mm2 (AWG 24 ... 16) Flexible: Without wire end ferrule 0.2 ... 1.5 mm2 (AWG 24 ...
E84AYCIB communication manual (INTERBUS) Commissioning Before initial switch-on 6 Commissioning During commissioning, system-specific data such as motor parameters, operating parameters, responses, and parameters for fieldbus communication are defined for the controller. For Lenze devices this is effected via the so-called codes. The codes of the controller and for communication are saved non-volatilely as a data set in the memory module.
E84AYCIB communication manual (INTERBUS) Commissioning Possible settings through DIP switch 6.2 Possible settings through DIP switch The following can be set through the DIP switch (S205): Number of process data words (PD) Switches: 1 ... 4 ( 35) Number of parameter data words (PCP) Switches: 5 and 6 ( 36) Baud rate Switch: 8 ( 37) Lenze setting: All switches "OFF" Switch 7 has no function.
E84AYCIB communication manual (INTERBUS) Commissioning Possible settings through DIP switch 6.2.1 Setting the number of process data words (PD) The number of process data words (PD) can be set via switches 1 ... 4 or code C13893 (for this, see Settings in the »Engineer« ( 38)). 0 ... 10 process data words can be used. The current setting is displayed in C13860/2. Note! The data word sum (PD + PCP) must amount to 1 ... 10 words.
E84AYCIB communication manual (INTERBUS) Commissioning Possible settings through DIP switch 6.2.2 Setting the number of parameter data words (PCP) The number of parameter data words (PCP) can be set via switches 5 and 6 or code C13892 (for this, see Settings in the »Engineer« ( 38)). 0, 1, 2 or 4 parameter data words can be used. The current setting is displayed in C13860/1. Note! The data word sum (PD + PCP) must amount to 1 ... 10 words.
E84AYCIB communication manual (INTERBUS) Commissioning Possible settings through DIP switch 6.2.3 Setting the baud rate The baud rate can be set via switch 8 or code C13894 (for this, see Settings in the »Engineer« ( 38)). The current setting of the baud rate is displayed in C13863/. DIP switch OFF 1 2 3 4 5 6 7 8 EDS84AYCIB EN 4.0 - 11/2010 ON Switch 8 Baud rate Max.
E84AYCIB communication manual (INTERBUS) Commissioning Settings in the »Engineer« 6.3 Settings in the »Engineer« Under the Settings tab in the »Engineer« you can set the following parameters: 38 Number of parameter data words (PCP, C13892) Number of process data words (PD, C13893) Baud rate (C13894) L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Commissioning Initial switch-on 6.4 Initial switch-on Documentation for the standard device Note! Observe the safety instructions and information on residual hazards contained in this documentation. Establishing communication In order to establish communication via an externally supplied communication module, the standard device must be switched on as well.
E84AYCIB communication manual (INTERBUS) Data transfer 7 Data transfer The INTERBUS master and controller communicate with each other by exchanging data telegrams via INTERBUS. The user data area of the data telegram contains parameter data or process data. In the controller, the parameter data and process data are assigned to different communication channels. Communication channels The process data channel transmits process data. – The process data are used to actuate the controller.
E84AYCIB communication manual (INTERBUS) Process data transfer Access to process data / PDO mapping 8 Process data transfer 8.1 Access to process data / PDO mapping The process data (MCI-PDOs) are transferred via the MCI interface. A maximum of 16 words is exchanged for each direction. The process data are accessed via the port blocks LP_MciIn and LP_MciOut. These port blocks are also referred to as process data channels. The port block LP_MciIn maps the MCI-PDOs received.
E84AYCIB communication manual (INTERBUS) Process data transfer Preconfigured port interconnection of the process data objects (PDO) Note! The »Engineer« screenshots shown in the following are only examples for the setting sequence and the resulting displays. The data in the display fields highlighted in white may differ from the ones of your project. 8.
E84AYCIB communication manual (INTERBUS) Process data transfer Freely configurating the port interconnection of the process data objects (PDO) 8.3 Freely configurating the port interconnection of the process data objects (PDO) How to freely configurate the port interconnection in the »Engineer«: 1. Go to the Process data objects tab to click the Go to application button. 2. Select the "MCI_IN" or "MCI_OUT" port blocks in the Ports tab via mouse-click and activate them with the Activate button.
E84AYCIB communication manual (INTERBUS) Process data transfer Freely configurating the port interconnection of the process data objects (PDO) 3. Click the Change variable... button. 44 L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Process data transfer Freely configurating the port interconnection of the process data objects (PDO) 4. The button serves to assign signals to the process data words in the Assignment signal --> function block dialog box. Select signals and then click the OK button. EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Process data transfer Freely configurating the port interconnection of the process data objects (PDO) Moreover you can assign signals to the individual control and status bits at the WORD_1... WORD_4 process data words via the and buttons. Select the signals and then click OK. 46 L EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Process data transfer Freely configurating the port interconnection of the process data objects (PDO) Tip! When the port blocks "LP_MciIn" and "LP_MciOut" are activated (see 1.), they will be visible in the »FB Editor«. Here you can also assign signals to the process data words. EDS84AYCIB EN 4.
E84AYCIB communication manual (INTERBUS) Parameter data transfer Addressing of the parameter data 9 Parameter data transfer 9.1 Addressing of the parameter data The parameter data are addressed via codes which are listed in the form of a code table in this communication manual and in the corresponding documentation for your controller.
E84AYCIB communication manual (INTERBUS) Parameter data transfer Supported PMS services 9.3 Supported PMS services Parameters are transferred via the PCP channel (PCP = Peripherals Communication Protocol). This is executed via PMS services. In the following, only parameters and their contents are given that are returned by the Lenze controllers. All other transfer parameters of the given PMS services can be obtained from the corresponding descriptions of the INTERBUS master.
E84AYCIB communication manual (INTERBUS) Parameter data transfer Supported PMS services 9.3.4 Read / Write The "Read" PMS service reads parameters from the controller. The controller outputs the requested parameter or an error message. The "Write" PMS service writes to parameters of the controller. The controller outputs a positive feedback or an error message. The following error messages can occur: 9.3.
E84AYCIB communication manual (INTERBUS) Parameter data transfer Supported PMS services 9.3.6 Identify The "Identify" PMS service provides information on how to identify the controller.
E84AYCIB communication manual (INTERBUS) Parameter data transfer Supported PMS services 9.3.7 Status The "Status" PMS service provides status information about the controller.
E84AYCIB communication manual (INTERBUS) Monitoring 10 Monitoring Communication fault If INTERBUS communication is interrupted, e.g. due to cable break or INTERBUS master failure, no process data are transmitted to the slave in the "IBS-ACTIVE" ( 57) status. After the time to be parameterised by the user in C13881 has elapsed, the response parameterised in C13880/1 is executed in the controller.
E84AYCIB communication manual (INTERBUS) Diagnostics LED status displays 11 Diagnostics For fault diagnostics, the INTERBUS module is provided with the LEDs on the front. Furthermore code C13861 can be used to query the current bus status (for this, see Diagnostics with the »Engineer« ( 57)). 11.1 LED status displays Note! In normal operation only the LEDs MS ( 55) and BS ( 56) should be lit constantly.
E84AYCIB communication manual (INTERBUS) Diagnostics LED status displays 11.1.1 Module status displays The LEDs MS, ME and DE display the module status. MS ME DE E84YCIB006 LED Colour Status MS Green On Description The communication module is supplied with voltage and has established a connection to the standard device. Blinking 200 ms 200 ms The communication module is supplied with voltage, but has not established a connection to the standard device.
E84AYCIB communication manual (INTERBUS) Diagnostics LED status displays 11.1.2 Fieldbus status displays The LEDs BS and BE display the fieldbus status. BS BE E84YCIB006 LED Colour Status BS Green Off Description The communication module is not active on the fieldbus. Data cycles are not executed. Blinking 200 ms 200 ms Communication has been established via the communication module. The INTERBUS is active. Data cycles are executed. BE Red On INTERBUS communication is interrupted.
E84AYCIB communication manual (INTERBUS) Diagnostics Querying the current bus status 11.2 Querying the current bus status Code C13861 displays the current bus status of the INTERBUS node: Value of C13861 [hex] Bus status Description 0xyyy0 IBS-INIT Initialisation 0xyyy1 IBS-ACTIVE The bus is active. Data cycles are executed. 0xyyy2 IBS-READY The bus is ready for operation. No data cycles are executed.
E84AYCIB communication manual (INTERBUS) Diagnostics Diagnostic data 11.3 Diagnostic data Pending diagnostic data are signalised by the master via an alarm message to the slave. Errors and warnings in the standard device and the plugged-in module are transmitted to the master as extended diagnostic messages. The diagnostic data can be viewed via the hexadecimal representation of the Engineering tool. Bytes Meaning Value [hex] 1 ... 6 Diagnostics block header 0x0010 001C 0100 7 ...
E84AYCIB communication manual (INTERBUS) Error messages Short overview (A-Z) of the INTERBUS error messages 12 Error messages This chapter provides the error messages of the communication module as a supplement to the error list in the software manual and the »Engineer« online help for the Inverter Drive 8400. 12.1 Software manual/»Engineer« online help for the Inverter Drive 8400 Here you'll find general information on diagnostics & fault analysis and error messages.
E84AYCIB communication manual (INTERBUS) Error messages Possible causes and remedies 12.2 Possible causes and remedies This chapter includes a list of all error messages of the communication module in numerically ascending order of the error number. Possible causes and remedies as well as responses to error messages are described in detail.
E84AYCIB communication manual (INTERBUS) Error messages Possible causes and remedies Internal error [0x01bc6010] Response (Lenze setting in bold) None System fault : Fault Setting: not possible Trouble Quick stop by trouble Warning locked Warning Information Cause Remedy Communication module is defective. Send communication module with error description to Lenze.
E84AYCIB communication manual (INTERBUS) Error messages Possible causes and remedies Invalid module configuration [0x01bc6430] Response (Lenze setting in bold) None System fault : Fault Setting: not possible Trouble Quick stop by trouble Warning locked Warning Information Cause Remedy Module configuration is faulty. Check and correct module configuration.
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module 13 Parameter reference This chapter supplements the parameter list and the table of attributes in the software manual and the »Engineer« online help for the Inverter Drive 8400 by parameters of the E84AYCIB communication module (INTERBUS). 13.1 Software manual/»Engineer« online help for the Inverter Drive 8400 Here you'll find general information about parameters.
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13852 Parameter | Name: Data type: UNSIGNED_16 Index: 10723d = 29E3h C13852 | All words to standard device Display of the process data words which are transmitted from the communication module to the standard device. • Subcodes 1 ... 16 display all process data words to the standard device. Maximally the first 10 words are relevant to the E84AYCIB INTERBUS module. Display area (min. value | unit | max.
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13861 Parameter | Name: Data type: BITFIELD_16 Index: 10714d = 29DAh C13861 | Bus status Display of the current bus status Querying the current bus status ( 57) Meaning of the resulting hexadecimal values: • 0xyyy0 = IBS-INIT • 0xyyy1 = IBS-ACTIVE • 0xyyy2 = IBS-READY Value is bit coded: Information Bit 0 Bit 0 ... ...
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13880 Parameter | Name: Data type: UNSIGNED_8 Index: 10695d = 29C7h C13880 | Reaction on communication failure Monitoring response in case of a communication fault A change in the monitoring response becomes effective immediately.
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13892 Parameter | Name: Data type: UNSIGNED_8 Index: 10683d = 29BBh C13892 | PCP - length Setting of the number of the parameter data words to be used (PCP) The setting is activated ...
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13894 Parameter | Name: Data type: UNSIGNED_8 Index: 10681d = 29B9h C13894 | Baud rate Setting of the baud rate The setting is activated ... • if all DIP switches (S205) are in the "OFF" position; • after executing the "11: Save start parameters" device command via standard device code C00002 and performing another mains switching of the communication module/drive afterwards.
E84AYCIB communication manual (INTERBUS) Parameter reference Parameters of the communication module C13920 Parameter | Name: Data type: BITFIELD_8 Index: 10655d = 299Fh C13920 | Display DIP switch setting Display of the current DIP switch position • The set PCP data length is displayed in C13860/1. • The set process data length is displayed in C13860/2. • The set baud rate is displayed in C13863.
E84AYCIB communication manual (INTERBUS) Parameter reference Table of attributes 13.2 Table of attributes The table of attributes contains information required for communicating with the controller via parameters. How to read the table of attributes: Column Meaning Code Parameter name Cxxxxx Name Parameter short text (display text) Text Index by which the parameter is addressed. The subindex for array variables corresponds to the Lenze subcode number.
E84AYCIB communication manual (INTERBUS) Parameter reference Table of attributes Table of attributes Code Name Index Data dec hex DS DA DT Access Factor R W C13850 All words to master 10725 29E5 A 16 UNSIGNED_16 1 ; C13851 All words from master 10724 29E4 A 16 UNSIGNED_16 1 ; C13852 All words to standard device 10723 29E3 A 16 UNSIGNED_16 1 ; C13853 All words from standard device 10722 29E2 A 16 UNSIGNED_16 1 ; C13860 Active settings 10715 29DB A 2 UNSI
E84AYCIB communication manual (INTERBUS) Index 14 Index Zahlen 9-pole Sub-D plug 29 9-pole Sub-D socket 29 A Abort (PMS service) 49 Access to process data 41 Activating altered settings 39 Active baud rate (C13863) 65 Active settings (C13860) 64 Addressing of the Lenze parameters 48 Addressing of the parameter data 48 All words from master (C13851) 63 All words from standard device (C13853) 64 All words to master (C13850) 63 All words to standard device (C13852) 64 Application as directed 14 Application
E84AYCIB communication manual (INTERBUS) Index 0x01bc8126 62 0x01bc8127 62 0x01bc8131 62 Establishing communication 39 EtherCAT error messages Causes and remedies 60 External voltage supply 31 Monitoring 53 Monitoring time for Interbus communication failure (C13881) 66 Mounting for standard devices 0.25 kW and 0.37 kW 24 Mounting for standard devices from 0.
E84AYCIB communication manual (INTERBUS) Index Settings in the »Engineer« 38 Specification of the bus cable 30 Status (PMS service) 52 Status displays (LEDs) 54 Supported PMS services 49 System error messages 59 T Table of attributes 70 Target group 7 Technical data 17 Terminals 16, 32 Terminology used 10 Terms 10 Type of node 17 U Using the communication module 14 V Validity of the documentation 7 Voltage supply 17, 31 W Write (PCP service) 50 74 L EDS84AYCIB EN 4.
© 11/2010 ) Lenze Drives GmbH Postfach 10 13 52 D-31763 Hameln Germany Service +49 (0)51 54 / 82-0 Lenze Service GmbH Breslauer Straße 3 32699 Extertal Germany 00 80 00 24 4 68 77 (24 h helpline) ¬ +49 (0)51 54 / 82-28 00 ¬ +49 (0)51 54 / 82-11 12 | Lenze@Lenze.de | Service@Lenze.de Þ www.Lenze.com EDS84AYCIB 13362260 EN 4.