Instruction Manual

Implemented CIP™ objects
General CIP objects
119
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Data mapping of the input assemblies
Supported service codes
Data component
[Bits 0 ... 7]
Class Instance
Number
Attribute
Name Number Name Number
Faulted [Bit 0] Control
Supervisor
0x29 1 Faulted 10
Warning [Bit 1] Control
Supervisor
0x29 1 Warning 11
Running1 (Fwd) [Bit 2] Control
Supervisor
0x29 1 Running1 7
Running2 (Rev) [Bit 3] Control
Supervisor
0x29 1 Running2 8
Ready [Bit 4] Control
Supervisor
0x29 1 Ready 9
CtrlFromNet [Bit 5] Control
Supervisor
0x29 1 CtrlFromNet 15
RefFromNet [Bit 6] AC Drive 0x2A 1 RefFromNet 29
At Reference [Bit 7] AC Drive 0x2A 1 AtReference 3
Drive State [Bits 0 ... 7] Control
Supervisor
0x29 1 State 6
Speed Actual [Bits 0 ... 7] AC Drive 0x2A 1 SpeedActual 7
Torque Actual [Bits 0 ... 7] AC Drive 0x2A 1 TorqueActual 11
Custom Input [Bits 0 ... 7]
Service code
[hex]
Name Description
0x0E Get_Attribute_Single Outputs the value of a certain attribute.
0x10 Set_Attribute_Single Changes the value of a certain attribute.