Implemented CIP™ objects
General CIP objects
121
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Instance error messages
Supported service codes
Error
code
[hex]
Extended
code
[hex]
Error designation Description
0x000 - SUCCESS No error
0x001 0x106 OWNERSHIP_CONFLICT The connection could not be established because another
connection has already occupied the required resources. It is
only possible to establish an "exclusive owner" connection to
the adapter.
0x001 0x119 NON-
LISTEN ONLY CONNECTION
NOT OPENED
The connection could not be established because there is no
"non-listen only" connection (input only, exclusive owner).
The "non-listen only" connection must be of the "multicast"
connection type.
0x001 0x127 INVALID_ORIGINATOR_TO_
TARGET_SIZE
The resulting length of the ports mapped in the receive
object PDO_RX0 does not correspond to the number of data
bytes of the assembly object instance 110 (0x6E, Custom
Output) defined in the scanner.
0x001 0x128 INVALID_TARGET_TO_
ORIGINATOR_SIZE
The resulting length of the ports mapped in the transmit
object PDO_TX0 does not correspond to the number of data
bytes of the assembly object instance 111 (0x6F, Custom
Input) defined in the scanner.
0x001 0x204 UNCONNECTED_REQUEST_
TIMED_OUT
The adapter does not respond to the establishment of the
connection.
• There might be no physical connection.
• The adapter is switched off.
• The adapter has an invalid IP configuration.
0x001 0x320 ACCESS_CONTENTION Manufacturer-specific error:
• The configurations of the assembly input and output
objects are mixed up.
The connection could not be established because another
connection has already occupied the required resources.
It is only possible to establish an "exclusive owner"
connection to the adapter.
0x001 0x111 ROUTER_EXT_ERR_RPI_
NOT_SUPPORTED
The RPI set for a connection is not supported.
•Min. class 1 RPI= 4ms
• Min. class-3-RPI = 10 ms
0x001 0x112 RROUTER_EXT_ERR_RPI_
VALUE_NOT_ACCEPTABLE
The RPI set for a connection is not supported.
•Min. class 1 RPI= 4ms
• Min. class-3-RPI = 10 ms
0x001 0x123 ROUTER_EXT_ERR_INVALID_
TO_CONNECTION_TYPE
The output image connection type is invalid or not
supported.
0x001 0x124 ROUTER_EXT_ERR_INVALID_
TO_CONNECTION_TYPE
The input image connection type is invalid or not supported.
0x001 0x12A ROUTER_EXT_ERR_INVALID_
CONSUMING_PATH
The path specification for the output data from the scanner
is invalid.
0x001 0x12B ROUTER_EXT_ERR_INVALID_
PRODUCING_PATH
The path specification for the input data to the scanner is
invalid.
Service code
[hex]
Name Description
0x54 Forward_Open Opens a CIP connection from the PLC to the target drive.
0x4E Forward_Close Closes a CIP connection from the PLC to the target drive.
0x0E Get_Attribute_Single Outputs the value of a certain attribute.