Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 30
Commissioning
Setting the IP configuration of the Inverter Drive 8400 motec
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the IP configuration of the Inverter Drive 8400 motec
The IP configuration is required for addressing the Inverter Drive 8400 motec to ensure that
communication between the PC/»Engineer« or the scanner and the drive can be effected via
EtherNet/IP. For this, an IP address, subnet mask, and gateway address must be allocated. You have
the following options to select the IP parameters for the Inverter Drive 8400 motec:
Setting via the EtherNet/IP configurator of the »Engineer«
( 31)
Setting via codes in the »Engineer«
( 33)
Setting via a BOOTP/DHCP server
( 35)
Setting via the TCP/IP Interface Object (0xF5)
( 35)
Note!
The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the EtherNet/IP network can
be established.
•Codes C13010
(IP address), C13011 (subnet mask), C13012 (gateway address), and
C13016
(multicast IP address) show the IP parameters currently used.
In the case of impermissible settings, the error message EtherNet/IP: Invalid IP
Parameters [0x01bc6533] ( 84) is output.