I/O data transfer (implicit messages)
Configuring I/O data
45
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.1 Configuring I/O data
The I/O data configuration is specified during the initialisation phase of the scanner (PDO
mapping).
To the scanner, up to 10 data words (max. 20 bytes) can be sent.
From the scanner, up to 8 data words (max. 16 bytes) can be sent.
•In the 111 (0x6F, Custom Input) assembly object instance, the I/O data is entered in the last two
words:
Data word Bits Function Value / description
Word 9 0
...
9
Analog input value
(0 ... 10 V)
10 V = 1000
10 Digital input 3 0 (FALSE) Open
1 (TRUE) Closed
11 Digital input 4 0 (FALSE) Open
1 (TRUE) Closed
12 Digital input 5 0 (FALSE) Open
1 (TRUE) Closed
13 Reserved
14 I/O status 0 (FALSE) Data in word 9/10 are not valid.
1 (TRUE) Data in word 9/10 are valid.
15 Connection status of the
drive
0 (FALSE) Drive is offline ("Stay alive" operation)
1 (TRUE) Drive is online
Word 10 0 RFR 0 (FALSE) Open
1 (TRUE) Closed
1 Digital input 1 0 (FALSE) Open
1 (TRUE) Closed
2 Digital input 2 0 (FALSE) Open
1 (TRUE) Closed
3 Digital input 3 0 (FALSE) Open
1 (TRUE) Closed
4 Digital input 4 0 (FALSE) Open
1 (TRUE) Closed
5 Digital input 5 0 (FALSE) Open
1 (TRUE) Closed
6
...
13
Reserved
14 I/O status 0 (FALSE) Data in word 9/10 are not valid.
1 (TRUE) Data in word 9/10 are valid.
15 Connection status of the
drive
0 (FALSE) Drive is offline ("Stay alive" operation)
1 (TRUE) Drive is online