I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 20 or higher
65
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Go to the "Module Definition" dialog window and make the connection settings.
The terms "input" and "output" refer to the point of view of the scanner:
Assembly input objects (input) are sent from the adapter to the scanner.
Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
Select "Exclusive Owner - Custom" connection.
If you use the Lenze technology applications or user-definable parameter sets in the
drive, the "Exclusive Owner - Custom" assembly object instance always has to be
selected.
•SetData type = INT.
The INT data type is exchanged via the ports MCI_IN and MCI_OUT of the Inverter Drives
8400. In case of the SINT data type, an additional PLC logic is required for conversion.
•SetTag Suffix = 1.
A tag suffix formulates a module-describing tag name.