Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 68
I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 20 or higher
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11. Complete the settings with OK.
The drive is inserted in the configuration tree under the "I/O Configuration".
The corresponding tags are created in the "Controller Tags".
The example shows the ...
input assembly tags as "MY_EIP8400_FROM_EDS:I1";
output assembly tags as "MY_EIP8400_FROM_EDS:O1";
If you click the "+" in front of the assembly tag name, all data contained in the assembly
tags are shown below it. You can create "alias tags" to reference to single bits of the
assembly tag.