Instruction Manual

Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 2.0 - 10/2013 98
Parameter reference
Parameters of the Communication Unit
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13844
C13845
C13846
C13847
Parameter | Name:
C13844 | Beacon Times
Data type: UNSIGNED_32
Index: 10731 = 0x29EB
Display of the beacon times (μs)
Subcodes Info
C13844/1 Beacon interval
C13844/2 Beacon timeout
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13845 | Beacon Frames
Data type: UNSIGNED_32
Index: 10730 = 0x29EA
Display of beacon frame information
Subcodes Info
C13845/1 Beacon frames - port X31
C13845/2 Beacon frame error - port X31
C13845/3 Beacon frames - port X32
C13845/4 Beacon frame error - port X32
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13846 | Address Conflict Detection
Data type: UNSIGNED_8
Index: 10729 = 0x29E9
Activation of the address conflict detection (ACD)
(Instance attribute 10 (SelectAcd) in the TCP/IP Interface Object (245 / 0xF5)
( 126))
Changing this value requires a reset of the device ("power off/on" or "type 0 reset").
Selection list (Lenze setting printed in bold)
0 Deactivated
1Enable
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13847 | Active Conflict Detection State
Data type: UNSIGNED_8
Index: 10728 = 0x29E8
Display of the status of address conflict detection (ACD)
Selection list (read only)
0 Not conflicted
1 Conflicted
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT