5 Function blocks
5.98 L_LdSyncOperation - master value connection
370
Lenze · 9400 function library · Reference manual · DMS 6.7 EN · 08/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.98.3 Operating mode 2: Free coupling
In this operating mode, the FB couples the axes of the master drive and the slave drive only via the
gearbox factors of the master drive/slave drive and the coupling factors parameterised in C05092/
1 and C05092/2.
Neither the feed constants nor the cycles of the master measuring system/slave measuring sys-
tem have any effect on the synchronism ratio.
Via C05092/1 and C05092/2 the revolution ratio is indicated, i.e. how many revolutions of the
master shaft (x axis) correspond to how many revolutions of the following axis (x axis).
The speed ratio between the slave drive and the master drive is calculated according to follo-
wing formula:
[5-61] Formula for operating mode 2
The conversion according to the formula above is remainder considered and hence drift-free
(consideration of remainders when performing divisions).
Application example: Wire drawing system with specification of the synchronism ratio K
y
The speed ratio between the master drive and the slave drive is calculated according to the formula
above, the synchronism ratio K
y
being considered as the C05092/1 and C05092/1 coupling factors:
dnYSpeedOut_s
dnXSpeedOut_s
-----------------------------------------
Gearbox constant Y
Gearbox constant X
---------------------------------------------------
Coupling factor Y (C05092/2)
Coupling factor X (C05092/1)
---------------------------------------------------------------------------
=
Master drive (wire drawing station 1)
Slave drive (wire drawing station 2)
Traversing speed
K
y
* traversing speed
Master drive (wire drawing station 1) Slave drive (wire drawing station 2)
Gearbox constant X 17 : 3 Gearbox constant Y 13 : 2
Feed constant X 160.0000 [mm] Feed constant Y 160.0000 [mm]
Coupling factor X
(C05092/1)
100 [%] Coupling factor Y
(C05092/2)
110 [%]
dnYSpeedOut_s
dnXSpeedOut_s
-----------------------------------------
13
2
------
17
3
------
------
110 [%]
100 [%]
-------------------
1.2618...==