5 Function blocks
5.133 L_SdRampGenerator - ramp function generator - S-ramp
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter
5.133.1 Loading the ramp function generator
By setting bLoadStartValue to TRUE the ramp function generator is loaded with the signal at
dnStartValue_n.
This value is accepted immediately and output to nOut_n. No s-shape ramp-up or ramp-down
takes place.
•As long as bLoadStartValue = TRUE , the ramp function generator is inhibited.
Parameter Possible settings Information
C04340 0.001 s 1000.000 Acceleration / deceleration time
Initialisation: 1.000 s
C04341 0.001 s 10.000 S-ramp time
Initialisation: 0.100 s
C04342
As of library V02.02.xx.xx
-200.000 % 200.000 Setpoint at the input
•Display of the dnIn_n input signal.
C04343
As of library V02.02.xx.xx
-200.000 % 200.000 Setpoint at the output
•Display of the dnOut_n output si-
gnal.