Owner's manual
9400 regenerative power supply module | Parameter setting
Oscilloscope
Internal variables (oscilloscope signals)
186 L EDS94ARNExxxx EN 2.3 - 06/2014
7.6 Internal variables (oscilloscope signals)
The system variables of the regenerative power supply module's internal control listed in
the following table can be recorded with the oscilloscope for diagnostics and
documentation purposes.
All further variables in the selection dialog of the oscilloscope are intended for closed-
loop controlled operation (in preparation).
Note!
The system variables of the internal control have a cycle offset of 2 ... 3 ms with
respect to all other variable values!
Variable Meaning
Common.bBrakeChopperActive Status signal "Brake chopper active"
Common.dnActualEfficiencyFactor Current cosine phi
• Scaling: 2
30
≡ 100 %
Common.dnI2tBrakeResistor Calculated utilisation of the brake resistor
• Scaling: 2
30
≡ 100 %
Common.dnIxtBrakeChopper Calculated utilisation of the brake chopper
• Scaling: 2
30
≡ 100 %
Current.dnActualCurrentPhaseU Current filter current (phase U)
Current.dnActualCurrentPhaseV Current filter current (phase V)
Current.dnActualCurrentPhaseW Current filter current (phase W)
Current.dnActualFilterCurrent Current filter current
Frequency.dnActualLineFrequency Current mains frequency
• Scaling: 2
30
≡ 4000 Hz
Phase.dnActualFilteredLinePhase Filtered commutation angle
• Scaling: 2
30
≡ 90°
Phase.dnActualLinePhase Unfiltered commutation angle
• Scaling: 2
30
≡ 90°
Power.dnActualPower Current active power
• Scaling: 2
30
≡ maximum active power (C00057)
Voltage.dnActualDCBusVoltage Current DC-bus voltage
Voltage.dnActualOutputVoltage Current output voltage