9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
244 L EDS94ARNExxxx EN 2.3 - 06/2014
Position value faulty [0x00910010]
Error during initialisation [0x00910011]
Block function in wrong MEC task [0x00910012]
Safety module: Incompatible with setting in C00214 [0x00920000]
Communication with safety module interrupted [0x00920001]
CAN module (MXI1): Bus off [0x009d0000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error If the error occurs frequently, please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error If the error occurs frequently, please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error If the error occurs frequently, please contact Lenze.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
A safety module is inserted in the regenerative power
supply module. The regenerative power supply module
does not support safety engineering.
Use SM0 module (without safety engineering).
Then, restart the controller.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Communication between the regenerative power supply
module and the safety module cannot be established.
Switch off regenerative power supply module, insert
SM0 safety module correctly, and switch on the
regenerative power supply module again.
If the problem occurs again, exchange the SM0 safety
module.
Response (Lenze setting printed in bold) Setting: C13595 ( Adjustable response)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
CANopen communication module in MXI1: "Bus-off"
state
Too many faulty telegrams received.
Defective cable (e.g. loose contact).
Two nodes with the same ID.
Eliminate disturbances (e.g. EMC).
Remove loose contact, screw down adapter.
Assign different node IDs.