Parameter | Name:
C00114 | Dig. input. x: Terminal polarity
Data type: UNSIGNED_8
Index: 24461
d
= 5F8D
h
"0" = positive logic (HIGH level = TRUE, LOW level = FALSE)
"1" = negative logic (HIGH level = FALSE, LOW level = TRUE)
Setting range (min. value | unit | max. value)
01
Subcodes Lenze setting Information
C00114/1 0 Terminal polarity - digital input 1 ... 8
C00114/...
C00114/8
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00118 | Dig. output. x: Terminal polarity
Data type: UNSIGNED_8
Index: 24457
d
= 5F89
h
"0" positive logic (TRUE HIGH level, FALSE LOW level)
"1" negative logic (FALSE HIGH level, TRUE LOW level)
Setting range (min. value | unit | max. value)
01
Subcodes Lenze setting Information
C00118/1 0 Terminal polarity - digital output 1 ... 4
C00118/...
C00118/4
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00121 | Filter temp. warning threshold
Data type: UNSIGNED_32
Index: 24454
d
= 5F86
h
Temperature threshold for filter temperature advance warning
The response to be initiated when the threshold is reached can be selected in C00584
.
Setting range (min. value | unit | max. value) Lenze setting
0 °C 150 135 °C
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00122 | Heatsink temp. warn. threshold
Data type: UNSIGNED_32
Index: 24453
d
= 5F85
h
Temperature threshold for heatsink temperature advance warning
The response to be initiated when the threshold is reached can be selected in C00582
.
Setting range (min. value | unit | max. value) Lenze setting
C8585 °C
Read access Write access CINH PLC STOP No transfer
Parameter | Name:
C00123 | Warning threshold device util.
Data type: UNSIGNED_32
Index: 24452
d
= 5F84
h
Adjustable threshold for I x t advance warning
The advance warning is sent if the device utilisation (C00064
) is higher than the set threshold.
The response to be initiated when the threshold is reached can be selected in C00604
.
Setting range (min. value | unit | max. value) Lenze setting
0 % 100 90 %
Read access Write access CINH PLC STOP No transfer