Manual

Wiring the device modules
Safety modules
6
114
EDK94SH366 DE/EN/FR/ES/IT 3.1
SM300
Functions
ƒ Safe torque off (STO)
(previously: s afe standstill, protection against unexpected start-up)
ƒ Safe stop 1 (SS1)
ƒ Connection of safety sensors
ƒ PROFIsafe safety bus connection
SSP94SM317
Fig.6-10 E94AYAD safety module
Please observe the following safety instructions and application notes to preserve the
certified safety engineering features and to ensure trouble-free and safe operation.
Danger!
Danger to life through improper installation
Improper installation of the safety engineering systems can cause an
uncontrolled restart of the drives.
Possible consequences:
ƒ Death or severe injuries
Protective measures:
Total cable length between X82 and the connected components (e.g. sensors,
devices, etc.) > 3 m:
ƒ It is essential to shield the cable installed between X82 and the connected
components:
Connect the shield at least to the shield support of the installation
backplane.
If possible, connect the shield to the connected component as well.
Total cable length between X82 and the connected components (e.g. sensors,
devices, etc.) < 3 m:
ƒ Unshielded wiring is permitted.