Owner manual
Electrical installation
DeviceNet connection
6
EDK94AYCDN DE/EN/FR/ES/IT 3.0
37
H1_E_INST−busltgslaenge
Plug connector assignment
The bus of the communication module is connected via the 5−pole plug connector with
double screw connection (X225).
E94YCDN001C
Designation Cable colour Description
V+ red External voltage supply
l U = 24 V DC
l I
max
= 170 mA
CAN_H white
Data line / input for bus terminating resistor (120W)
SHIELD Shielding
CAN_L blue
Data line / input for bus terminating resistor (120W)
V− black Reference potential for external voltage supply