Manual
Technical data
Rated data
2
EDK94AZHY25 DE/EN/FR/ES/IT 2.2
33
H1_Daten−BemDat_Br_E94AZHx0025
Rated data
Input data
Voltage Frequency Current [A]
Number
of
phases
Type [V] [Hz] max. +45 °C
max. +55 °C
E94AZHY0025 230/290 50/60 0.75/0.75 0.54/0.54 1
Temperature in the control cabinet
Output data
Voltage Frequency Current [A]
Number
of
phases
Type [V] [Hz] max. +45 °C
max. +55 °C
E94AZHY0025 205/260 0 (DC) 0.75/0.75 0.54/0.54 1
Temperature in the control cabinet
Area Values
Input voltage AC 230 V (180 ... 317 V), 45 ... 65 Hz
Output voltage DC 205 V With mains voltage of AC 230 V
Brake current 0.1 ... 0.75 A
Cable protection Recommendation: 5 A, tripping characteristic "B" or "C"
Control input
Control voltage
Internal
Control current
Protective function
Max. connectable cable
cross−section
2.5 mm
2
AWG 12
Maximum cable length 150 m