Instruction Manual
Technical data
General data and operating conditions
4
38
EDK94AZRP DE/EN/FR/ES/IT 6.0
4 Technical data
4.1 General data and operating conditions
Conformity and approval
Approval
UR UL508 Industrial Control Equipment, Underwriter
Laboratories (File-No. E219022) for USA and Canada
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
IT systems Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!
Protection of persons and equipment
Enclosure
EN 60529
IP20
Not in the wire range of the
terminals
NEMA 250 Protection against
contact to type 1
Earth leakage current IEC/EN 61800-5-1 >3.5mAAC
>10mADC
Observe regulations and
safety instructions!
Insulation resistance IEC/EN 61800-5-1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II