Instruction Manual

Technical data
Rated data
4
40
EDK94AZRP DE/EN/FR/ES/IT 6.0
4.2 Rated data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f[Hz]
3/PE AC 230 180-0%...264+0% 45-0%...65+0%
3/PE AC 400 320-0%...440+0% 45-0%...65+0%
3/PE AC 500 400-0%...550+0% 45-0%...65+0%
Voltage Freq. Current [A] Current [A]
Number
of phases
[V] [Hz] max. +45° C max. +55° C
E94AZRP0084 230/400/500 50/60 8/8/8 6/6/6 3
E94AZRP0294 230/400/500 50/60 29/29/29 21.8/21.8/21.8 3
E94AZRP0294
2)
400/500 50/60 24.5/24.5 15.3/15.3 3
Temperature in the control cabinet
2)
For i700 mounting: mains connection at the bottom, output at the top
Power loss Inductance Voltage drop
P
loss
[W] L[mH] U[V]
E94AZRP0084 20
E94AZRP0294 50