Mounting steps
How to connect the filter:
1. De−energise the control cabinet and fuse it against re−energisation.
2. Wait for at least 3 minutes before checking the standard device for isolation from
supply.
3. Wire the filter input cables and the filter output cables according to the connection
plan.
Observe tightening torque.
4. Wire the DC−bus cables (+UG/−UG) according to the connection plan.
The terminals +UG und −UG must be connected using the same cable cross−section
as in the motor cable.
Observe tightening torque.
Only for types with thermal contact:
5. Wire the terminals of the thermal contact 3.
Integrate the thermal contact into the monitoring system so that the mains
supply is switched off when the filter is overheated.
NC contact, switching capacity: 250 V AC / 1.6 A
Connect the twisted cables.
Observe tightening torque.
) Note!
When commissioning, please observe that operation is only permissible
ƒ with V/f or V/f
2
characteristic control
ƒ at a switching frequency of 8 ... 16 kHz
Ensure that the automatic switching frequency reduction is deactivated (see
documentation of the standard device). The filter will overheat at a switching
frequency of <8 kHz.