The following must be observed when using sinusoidal filters:
ƒ Use sinusoidal filters only together with standard asynchronous machines 0 ... 550 V.
ƒ Operation is only permissible using a V/f or V/f
2
characteristic control.
ƒ Operation is only permissible using a switching frequency of 2 ... 4 kHz.
– Ensure that the automatic switching frequency reduction is deactivated (see
documentation of the standard device).
ƒ Limit the output frequency to maximally 150 Hz.
ƒ Please note when dimensioning the controller that the controller has an additional load
of 10 ... 15 %.