Manual

Technical data 2
15
EDKZS3Y200 DE/EN/FR/ES/IT 1.1
2 Technical data
Standards
Conformity CE Low−Voltage Directive
Approval UR UL508, Industrial Control
Equipment, Underwriter
Laboratories (File−No. E219022) for
USA and Canada
Operating conditions
Climatic conditions Class 3K3 according to EN 50178 Without condensation, average
relative humidity 85 %
Permissible ambient
operating temperature
−10 °C ... +55 °C
Above 40 °C, the rated current I
r
must be reduced by 2.5 %/°C
Permissible installation
height
0 ... 4000 m amsl
Above 1000 m, the rated current I
r
must be reduced by 5 %/1000 m
Vibration resistance Accelerational stability up to 1 g EN50178, IEC61800−5−1 and
Germanischer Lloyd, general
conditions
Degree of protection IP20 (protection against contact to NEMA 250 type 1)
Mounting position Vertical with fixing bracket below
Connecting cables
Controller
« filter
As short as possible, shielded
Filter « motor Max. 200 m shielded or max. 300 m unshielded
Rated data
Type U [V] f
ch
[kHz] I
r
[A] P
V
[W] L [mH] m [kg]
EZS3−115A200
0 ... 550 V AC 2 ... 4
115 360 0.7 66
EZS3−150A200 150 400 0.5 69
U Voltage range PV Power loss
f
ch
Switching frequency L Inductance
I
r
Rated current m Mass