Manual

Electrical installation
Mounting steps
4
19
EDKZS3Y200 DE/EN/FR/ES/IT 1.1
4.3 Mounting steps
M
3~
1U1
1U2
1V1
1V2
1W1
1W2
EZS3-xxxA200
xxxx
UVW
SSP94SF107 SSP94SF004
SSP94SF109
x Stripping length depends on the filter size
How to connect the filter:
1. Loosen the four screws and remove the terminal cover .
2. Connect the filter input cable to terminals 1U1, 1V1, 1W1.
Connect the filter output cable to terminals 1U2, 1V2, 1W2.
Use shielded cables.
Connect the two PE conductors to the PE stud using ring cable lugs
(PE connection must comply with EN 50178).
Observe tightening torques.
3. Turn down the shield and connect it to the shield sheet (PES) with a surface
as large as possible.
Fix the shield with a metal cable tie or hose clip .
Use an additional cable tie for strain relief .
4. Insert the terminal cover and fix it with four screws .