Submittal Sheet

THERMOSTATIC
MIXING VALVES
Submittal Data Sheet S-2018-LF
April, 2020
LV-985-SW-LF____
10-216 GPM (37.9-818 l/min)
Thermostatic Water Mixing Valve with 10
GPM (37.9 l/min) minimum flow capacity
2 sweat inlets, 2 sweat outlet (51mm x
51mm)
Integral combination checkstops with strainers
and wall support
125 PSI (8.6 BAR) maximum operating
pressure
Copper encapsulated thermostatic assembly
with Stainless steel shuttle
Locking temperature regulating handle
Temperature adjustment range, 95-135ºF (35-
57ºC) **
Top or bottom supply connections
Internal parts of Lead-Free bronze, and
stainless steel
Rough Bronze Finish
OPTIONS
____SUFFIX LWS Less wall support
____SUFFIX BDT Ball valve with dial
thermometer (shipped loose)
Note: CP, chrome plated not available
NOTE: Leonard Valve Company reserves the right of product or design
modification without notice or obligation
*NOTE: A locking temperature regulator set for 120°F (49°C), is
simply a mechanical setting to prevent unauthorized temperature
set point changes. If incoming water is hotter than 150°F (65.5°C),
the temperature of the factory test, the valve may deliver in excess
of 120°F. MUST BE RESET BY THE INSTALLER
PRESSURE DROP
PSI
BAR
GPM
l/min
5045403530252015105
10
37.9
VALVE
LV-985
3.43.12.82.42.11.71.410.70.3
216205193181168154
139120
9971
818776731685636583
526
454375
269
MIN
+
FLOW
(0.3)
10
(0.7)
15
(1.0)
20
(1.4)
25
(1.7)
30
(2.1)
35
(2,4)
40
(2.8)
45
(3.1)
50
(3.4)
PRESSURE DROP
PSI(BAR)
220(833)
FLOW RATE
GPM(l/min)
60(227)
0
80(303)
100(379)
120(454)
140(530)
160(606)
180(681)
200(757)
5
+NOTE: The valve will maintain temperature with 0.5GPM flow from
the domestic hot water loop when properly installed near the hot water
source with a continuously operating recirculation pump.
NOTE: Sweat inlets & outlet, checks shipped loose
ECO-MIX
ASSE 1017 Certified
cUPC Certified
This product is certified to meet Low Lead requirements of
wetted surface area containing less than 0.25% lead by
weight
**NOTE: For temperatures outside of this valve’s stated range, please
see our line of bi-metal valves.
WARNING: This product can expose you to
chemicals including lead, which is known to the
State of California to cause cancer. For more
information, go to www.P65Warnings.Ca.gov
!

Summary of content (2 pages)