Submittal Sheet
THERMOSTATIC
MIXING VALVES
Submittal Data Sheet S-2018-LF
April, 2020
LV-985-SW-LF____
10-216 GPM (37.9-818 l/min)
• Thermostatic Water Mixing Valve with 10
GPM (37.9 l/min) minimum flow capacity
• 2” sweat inlets, 2” sweat outlet (51mm x
51mm)
• Integral combination checkstops with strainers
and wall support
• 125 PSI (8.6 BAR) maximum operating
pressure
• Copper encapsulated thermostatic assembly
with Stainless steel shuttle
• Locking temperature regulating handle
Temperature adjustment range, 95-135ºF (35-
57ºC) **
• Top or bottom supply connections
• Internal parts of Lead-Free bronze, and
stainless steel
• Rough Bronze Finish
OPTIONS
____SUFFIX LWS Less wall support
____SUFFIX BDT Ball valve with dial
thermometer (shipped loose)
Note: CP, chrome plated not available
NOTE: Leonard Valve Company reserves the right of product or design
modification without notice or obligation
*NOTE: A locking temperature regulator set for 120°F (49°C), is
simply a mechanical setting to prevent unauthorized temperature
set point changes. If incoming water is hotter than 150°F (65.5°C),
the temperature of the factory test, the valve may deliver in excess
of 120°F. MUST BE RESET BY THE INSTALLER
PRESSURE DROP
PSI
BAR
GPM
l/min
5045403530252015105
10
37.9
VALVE
LV-985
3.43.12.82.42.11.71.410.70.3
216205193181168154
139120
9971
818776731685636583
526
454375
269
MIN
+
FLOW
(0.3)
10
(0.7)
15
(1.0)
20
(1.4)
25
(1.7)
30
(2.1)
35
(2,4)
40
(2.8)
45
(3.1)
50
(3.4)
PRESSURE DROP
PSI(BAR)
220(833)
FLOW RATE
GPM(l/min)
60(227)
0
80(303)
100(379)
120(454)
140(530)
160(606)
180(681)
200(757)
5
+NOTE: The valve will maintain temperature with 0.5GPM flow from
the domestic hot water loop when properly installed near the hot water
source with a continuously operating recirculation pump.
NOTE: Sweat inlets & outlet, checks shipped loose
ECO-MIX
™
ASSE 1017 Certified
cUPC Certified
This product is certified to meet Low Lead requirements of
wetted surface area containing less than 0.25% lead by
weight
**NOTE: For temperatures outside of this valve’s stated range, please
see our line of bi-metal valves.
WARNING: This product can expose you to
chemicals including lead, which is known to the
State of California to cause cancer. For more
information, go to www.P65Warnings.Ca.gov
!