Install Instructions
BULLETIN G-26
August, 2018
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
Maximum Operating Pressure 125PSI (860 KPA) for Hot and Cold Water.
INSTALLATION
CAUTION
All thermostatic water mixing valves have limitations. They will not provide the desired accuracy outside of their flow
capacity range. Consult the capacity chart on page 6. Minimum flow must be no less than as shown.
REMEMBER! THIS IS A CONTROL SYSTEM WHICH MUST BE CLEANED AND MAINTAINED ON A
REGULAR BASIS (SEE MAINTENANCE GUIDE AND RECORD MGR-1000).
INSTALLATION ADJUSTMENT SERVICE
TYPE TM-26, TM-26-LF
IMPORTANT! Provide valve serial number (stamped on cover of valve) when ordering parts!!
Valve manufactured after July 2007 starting with serial # TM26272
ASSE
1017
OUTLET
HOT INLET
COLD INLET
1. Valve should be installed at a location where it
can easily be cleaned, adjusted or repaired.
2. Connect the hot water and cold water as shown
above.
3. Valve has integral checkstops, for ease of
servicing.
4. A shutoff valve must be installed on the outlet
pipe. Type TM valves do not have a built-in
shutoff.
5. Use solder or pipe cement sparingly. Supply
pipes should be flushed before the valve is
connected. Flush outlet pipe and valve as soon
as it is connected.
!