Brochure

2
ASSE 1071
SINGLE EYEWASH OR EYE / FACE WASH
Leonard Thermostatic
Water Mixing Valves
Controls water temperature to provide
tepid water for emergency showers,
eyewash and eye/face wash units
DURA-trol
®
bi-metal thermostatic
control
Locked temperature regulator set for
85°F (29°C)
High temperature limit stop set for
90°F (32°C)
Internal cold water by-pass on failure
of hot water supply standard on all
models
On failure of hot water supply, internal
cold water by-pass delivers cold water
to the emergency xture, minimum of
4 GPM at 30 PSI
ANSI/ISEA Z358.1-2014 requires
water to emergency equipment
to be “tepid”
Optional systems with temperature
override protection available
All systems are factory tested
before shipment
On failure of cold water supply, hot
water is shut down
Color coded outlet dial thermometer
to view temperature
Toll-free technical support
TA-350-LFTA-300-LF TA-300-LF-STSTL-REC
Locked temperature
setting at 85°F (29°C)
DURA-trol
®
solid bi-metal
thermostat not subject to
failure due to rupture or
fatigue
Internal parts of bronze,
brass and stainless steel
Models
TA-300-LF Eye/Face Wash, 1/2” inlets, 1/2” outlet,
2 - 9 GPM (7.6-34 l/min)
TA-350-LF Eye/Face Wash, 3/4” inlets, 3/4” outlet,
2 - 9 GPM (7.6-34 l/min)
TA-300-LF Standard System / TA-350-LF Dual
System with Temperature Override Protection
Selection Guide
Temperature Override Protection (TA-350-LF only)
A redundant thermostatic control valve on the outlet opens on temperature rise
at 90°F (32°C) to introduce cold water and maintain tepid ow to the xture