Brochure

© 2018 Leonard Valve | www.leonardvalve.com
3
SINGLE / MULTIPLE DRENCH
OR COMBINATION SHOWERS
DURA-trol
®
solid
bi-metal thermostat
directly linked to
valve porting
Internal parts of
bronze, brass and
stainless steel
Locked temperature
adjustment setting
Adjustable high temperature
limit stop
Union angle checkstops
(with strainers) for top or
bottom supplies
TM-600-LF, TM-800-LF Standard System /
TM-850-LF Dual System with Temperature
Override Protection Selection Guide
TM-850-LFTM-600-LF-STSTL-REC-VIEW
TM-600-LF
Models
TM-600-LF Single or Combination Shower, 3/4” inlets, 1” outlet,
3 - 51 GPM (11 - 193 l/min)
TM-800-LF Single or Multiple Drench or Combination Shower,
1” inlets, 1-1/4” outlet, 3 - 56 GPM (11 - 212 l/min)
TM-850-LF Single or Multiple Drench or Combination Shower,
1-1/4” inlets, 1-1/4” outlet, 3 - 56 GPM (11 - 212 l/min)
Leonard Thermostatic
Water Mixing Valves
Controls water temperature to provide
tepid water for emergency showers,
eyewash and eye/face wash units
DURA-trol
®
bi-metal thermostatic
control
Locked temperature regulator set for
85°F (29°C)
High temperature limit stop set for
90°F (32°C)
Internal cold water by-pass on failure
of hot water supply standard on all
models
On failure of hot water supply, internal
cold water by-pass delivers cold water
to the emergency xture, minimum of
20 GPM at 30 PSI
ANSI/ISEA Z358.1-2014 requires
water to emergency equipment
to be “tepid”
Optional systems with temperature
override protection available
All systems are factory tested
before shipment
On failure of cold water supply, hot
water is shut down
Color coded outlet dial thermometer
to view temperature
Toll-free technical support
Temperature Override Protection (TM-850-LF only)
A redundant thermostatic control valve on the outlet opens on temperature rise
at 90°F (32°C) to introduce cold water and maintain tepid ow to the xture