Brochure

4
SINGLE / MULTIPLE DRENCH
COMBINATION SHOWERS
TM-5100-LF Standard System / TM-5125-LF
Dual System with Temperature Override
Protection Selection Guide
TM-5100-LF TM-5100-LF-STSTL-RECTM-5125-LF
Options
CP Chrome Plated Finish
IT Inlet Thermometers
BWE-EXP Exposed Baked White Steel Cabinet
BWE-REC Recessed Baked White Steel Cabinet
VIEW Viewport in Door (Standard except for TA-300-LF)
TOP Top Inlets
Leonard Thermostatic
Water Mixing Valves
Controls water temperature to provide
tepid water for emergency showers,
eyewash and eye/face wash units
DURA-trol
®
bi-metal thermostatic
control
Locked temperature regulator set for
85°F (29°C)
High temperature limit stop set for
90°F (32°C)
Internal cold water by-pass on failure
of hot water supply standard on all
models
On failure of hot water supply, internal
cold water by-pass delivers cold water
to the emergency xture, minimum of
40 GPM at 30 PSI
ANSI/ISEA Z358.1-2014 requires
water to emergency equipment
to be “tepid”
Optional systems with temperature
override protection available
All systems are factory tested
before shipment
On failure of cold water supply, hot
water is shut down
Color coded outlet dial thermometer
to view temperature
Toll-free technical support
Models
TM-5100-LF Multiple Drench or Combination Showers, 1-1/4” inlets,
1-1/2” outlet, 3 - 126 GPM (11 - 477 l/min)
TM-5125-LF Multiple Drench or Combination Showers, 1-1/4” inlets,
1-1/2” outlet, 3 - 126 GPM (11 - 477 l/min)
1360 Elmwood Ave., Cranston, RI 02910
TF: 800.222.1208 | P: 401.461.1200
F: 401.941.5310 | www.leonardvalve.com
LV-115 REV 06/2018 | ©2018 LEONARD VALVE COMPANY | PRINTED IN THE U.S.A
Temperature Override Protection (TM-5125-LF only)
A redundant thermostatic control valve on the outlet opens on temperature rise
at 90°F (32°C) to introduce cold water and maintain tepid ow to the xture