Submittal Sheet
Submittal Data Sheet S-176G8-LF
August 2018
1360 Elmwood Avenue, Cranston, RI 02910 USA
Phone: 401.461.1200 Fax: 401.941.5310
Email: info@leonardvalve.com
Web Site: http://www.leonardvalve.com
Engineer's Approval Job # ________________
Arch/Eng. ____________
Contractor ____________
EMERGENCY
MIXING
VA LV ES
CAUTION! All thermostatic water mixing valves have limitations. They will NOT
provide the desired accuracy outside of their flow capacity range. Consult the Flow
Capacity Chart and DO NOT OVERSIZE. Minimum flow must be no less than as
indicated.
*NOTE: A limit stop, set for 90F(32C), is simply a mechanical setting to prevent
excessive handle rotation. If incoming water is hotter than 135F(57C), the temperature
of the factory test, the valve when turned to full HOT may deliver water in excess of
90F and the limit stop MUST BE RESET BY THE INSTALLER
Exposed Assembly for Drench or
Combination Emergency Shower
3 - 56 GPM (11 - 212 l/min) flow rate
up to 45 PSI (3.1 bar) system pressure drop
TM-800-LF
ASSE 1071 Certified
CSA Certified
__TM-800-LF
EMERGENCY WATER MIXING VALVE
DURA-trol® solid bimetal thermostat directly linked to valve porting
to control the intake of hot and cold water and compensate for supply
temperature and pressure fluctuations DURA-trol® is highly
responsive and cannot be damaged by extremes in temperature
Thermostatic Mixing Valve can be set to the correct temperature for
the application
Locking type temperature regulator to prevent accidental movement
set for 85ºF (29ºC)
Mixing valve will close down on failure of cold water supply
Mixing Valve with special internal cold water bypass capable of 20
GPM (76 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply
Adjustable high temperature limit stop * set for 90ºF (32ºC)
Full 1” top or bottom inlets and 1 ¼” top outlet
Integral wall support
Dial thermometer (range 0 to 140°F, -10 to 60°C)
Rough bronze finish
Union angle checkstops on inlets
Compliance…………ANSI Z358.1
Maximum supply temperature 180 °F (82°C)
Maximum supply pressure 125 PSI (8.6 Bar)
OPTIONS
__ CP- Chrome plated finish
__ IT- Inlet thermometers (range 0 to 140°F, -10 to 60°C)
°C
°F
DRAIN
SUPPLIED
BY OTHERS
C
H
EMERGENCY VALVE
THERMOSTATIC
LEONARD
SUFFIX IT
ECO-MIX
™
R
C
US
This product is certified to meet Low Lead
requirements of wetted surface area containing less
than 0.25% lead by weight
NOTE: Performance specifications above applicable when
valve is tested to conditions specified per ASSE 1071
!
WARNING: This product can expose you to
chemicals including lead, which is known to the
State of California to cause cancer. For more
information, go to www.P65Warnings.Ca.gov
+NOTE: The valve will maintain temperature with 0.5GPM flow from
the domestic hot water loop when properly installed near the hot water
source with a continuously operating recirculation pump.