User's Manual

Dip Switches 1-4
Single Pole (One Location)
Wireless Occupancy Sensor Products
Cat. No. WSS10, WSC04, WSC15, and WSS0S
Incandescent 800W @ 120V
Ballast 1200VAC @ 120V, 2700VA @ 277V
120-277VAC, 50-60Hz, Motor:
1
/
4
HP @ 120V
INSTALLATION INSTRUCTIONS
WARNINGS AND CAUTIONS:
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult a qualified electrician.
WSS0S Wireless Remote Switch can be used for additional switches (3-way and 4-way), no wires necessary.
WARNINGS AND CAUTIONS:
Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.
Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.
Recommended minimum wall box depth is 2-1/2”.
Tools needed to install your Switch:
Slotted/Phillips Screwdriver Electrical Tape Pliers
Pencil Cutters Ruler
Wire Nuts
DIP SWITCH SETTINGS:
Manual ON / Auto ON mode: (factory: manual mode) Occupancy Sensor
WSC** - Auto mode can be enabled with the use of additional (3) AAA
batteries or a 5-24VDC connection.
Walk-through: On or Off (can be used only in Auto-ON mode)
Timeout: 2, 10, 20, 30min
Cat. No. WSS10 has a single switch pad that toggles the relay and its
corresponding load, ON and OFF. If the relay is OFF, the relay will turn
ON when the push-button is pressed, and remain ON in the presence of
motion. In the absence of motion, the Sensor Unit will Time-Out and turn
relay OFF. If in Auto ON/Manual OFF, time delay will start once space is
vacant.
NOTES:
When the lights are on, the Motion Indicator LED will blink red (1 blink
per minute) every time motion is detected.
When the Time-Out expires and the relay turns OFF, a 30 second
vacancy confirmation exists to turn the relay back ON.
• In Manual-ON mode, the button must be pressed to turn the lights ON.
In the absence of motion, the unit will Time-Out and turn the lights OFF.
LEARN MODE:
When using the Wireless Occupancy Products together, they must
LEARN the other devices to perform as desired.
WSC04 and WSC15 – Wireless Occupancy Sensor – has learn button
on device, under front plastic tab
WSS10 – Wireless Momentary Control Switch – use switch pad for
learning
WSS0S – Wireless Remote Switch – use switch pad for learning
Programming – using Momentary Switch (WSS10)
To enter programming, press and hold the switch pad for 15 seconds
When in programming mode,
1 AMBER LED flash, 1 second pause = in programming
There are 2 modes in programming, LEARN and CLEAR modes. Tap the
switch pad to select which mode you would like.
• 1 AMBER LED flash = LEARN mode
• 2 AMBER LED flashes = CLEAR mode
Once you have selected the desired programming mode, press and hold
the pad again for 5 seconds to ENTER the desired mode.
• Learn mode:
• 1 Red flash = no learned devices
• 1 Green flash = 1 learned devices
• 2 Green flashes = 2 learned devices
• 3 Green flashes = 3 learned devices
• Etc. (up to 6 devices)
• On remote switch or occupancy sensor, you must press the switch pad
to send a signal for learning.
• AMBER LED on for 2 seconds = acknowledgement, device is
learned
• GREEN LED on for 2 seconds = device is unlearned
INSTALLING YOUR SWITCH
NOTE: Use check boxes when Steps are completed.
Changing the color of your Switch:
Color change kits are available from Leviton. To change color of frame,
proceed as follows:
Line up tabs and
press in side to attach
Push in side
at tab to release
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&/./&&
/./&&
/./&&
/./&&
/./&&
WARNING: TO AVOID FIRE SHOCK OR DEATH; TURN
OFF POWER at circuit breaker or fuse and test that power is
off before wiring!
Step 1
B
K
W
H
Black Wire (BK)
Blue Wire (BL)
4
2
White Wire (WH)
1
3
Single Pole Wiring Application:
Step 3a
2
4
3
1
Single Pole
1. Line (Hot)
2. Neutral
3. Ground
4. Load
Identifying your wiring application (most common):
NOTE: If the wiring in your wall box does not resemble this
configuration, consult a qualified electrician.
Step 2
Step 3b cont'd
Factory Settings: The sensor is shipped from the factory to work in almost
all situations, without any adjustments. The factory settings are: Manual
mode, when entering the room, the wireless momentary switch will need
to be turned ON. Wireless occupancy sensor will keep the lights on until
the room is vacant then turn the lights OFF after timeout period. The PIR
technology is active. Factory time-out is 10 min.
Time-Outs: The Sensor has four time-out settings: 2, 10, 20, or 30 min.
• Fixed Time-Out: The value of this time-out is user selected through the
use of the Dip Switch Settings.
Walk-Through Time Delay: The walk-through feature, which is only active
in the Auto-On mode, is useful when a room is momentarily occupied.
With this feature, the Sensor will turn the lights OFF shortly after the
person leaves the room. The walk-through feature works in the following
manner: When a person enters the room, the lights will turn ON. If the
person leaves the room before the walk-through time-out of 2.5 minutes,
the Sensor will turn the lights OFF within 2.5 minutes of no occupancy
detected. If the room is occupied for longer than 2.5 minutes, the Sensor
will enter the Occupied Mode with the time-out duration specified by the
Dip Switch setting.
Hot (Bla c k )
Neutral (White)
Load
Swit c h
BK WH
Bla c k
White
BL
Line
120 V A C , 60H z
WIRING SWITCH:
Connect wires per WIRING DIAGRAM below as follows:
Connect (Hot) wire from wall box to black wire on switch.
Connect (Load) wire in wall box to blue wire on switch.
Connect (Neutral) wire in wall box to white wire on switch.
NOTE: For NO Neutral model, white wire will not be available.
NOTE: For 3-way applications, 4-way and more, use the
WSS0S Wireless Remote.
Step 3b cont'd
Single Pole Wiring Application:
Step 3b
NOTE: To access dip switch settings, lift up the bottom of the
switch pad.
DIP SWITCH SETTINGS
Dip Switch OFF Position ON Position
1 Auto ON/Manual OFF Manual ON
2 Walk Through OFF Walk Through ON
2 Min Time-Out OFF Position ON Position
3 X -
4 X -
10 Min Time-Out OFF Position ON Position
3 X -
4 - X
20 Min Time-Out OFF Position ON Position
3 - X
4 X -
30 Min Time-Out OFF Position ON Position
3 - X
4 - X