Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
continued from page 109
other Class 2 circuits. Separation from other circuits shall
comply with 725.136.
(D) Protection. Wiring shall comply with the requirements
of 300.4 and be installed in a raceway, armored or metal-
clad cable, or cable tray.
Exception No. 1: Section 700.11(D) shall not apply to wiring that does not
exceed 1.83 m (6 ft) in length and that terminates at an emergency luminaire
or an emergency lighting control device.
Exception No. 2: Section 700.11(D) shall not apply to locked rooms or locked
enclosures that are accessible only to qualied persons.
Informational Note: Locked rooms accessible only to qualied
persons include locked telecommunications rooms, locked electrical
equipment rooms, or other access-controlled areas.
Expert Analysis
A new section has been added to address Class 2
powered emergency lighting systems. Due to new
technologies, such as power over ethernet and
low-power consumption LED luminaires,
these systems utilize Class 2 conductors to deliver
power, control signals, or both from a central device
to one or more emergency luminaires.