FAQ

83
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
and the marking on the equipment nameplate is not less than the current
marked on the fan or blower motor nameplate, the full-load current marked
on the nameplate of the appliance shall be used to determine the ampacity of
branch-circuit conductors, in addition to the current ratings of the following:
(1) Disconnecting means
(2) Motor controllers
(3) Short-circuit and ground-fault protective devices
(4) Separate overload protective devices
Exception No. 3: For a listed motor-operated appliance that is marked with
both motor horsepower and full-load current, the motor full-load current
marked on the nameplate of the appliance shall be used instead of the
horsepower rating on the appliance nameplate to determine the ampacity of
branch-circuit conductors, in addition to the current ratings of the following:
(1) Disconnecting means
(2) Motor controllers
(3) Short-circuit and ground-fault protective devices
(4) Separate overload protective devices
(2) Nameplate Values. The motor nameplate current ratings
shall be used to determine the values for the following:
(1) Separate motor overload protection
(2) For motors built for low speeds (less than 1200 RPM),
high torques, canned pumps, or multispeed motors, the
following:
a. Ampacity of conductors
b. Current ratings of switches
c. Current ratings of branch-circuit short-circuit and ground-
fault protection
(3) Large motors exceeding the values in Part XIV shall use
the nameplate current rating for conductor sizing.
Expert Analysis
A revision has been made to clarify the requirements
when applying nameplate or table values for general
motor applications.
continued on page 84
Sizing Using Table