440.11 General. Disconnecting means shall be capable of
disconnecting air-conditioning and refrigerating equipment,
including motor-compressors and controllers, from the
circuit conductors. If the disconnecting means is readily
accessible to unqualied persons, any enclosure door or
hinged cover of a disconnecting means enclosure that
exposes energized parts when open shall require a tool to
open or be capable of being locked.
Expert Analysis
A new sentence has been added to address the
protection of unqualified persons in the vicinity of this
equipment. Section 440.14 already addresses location.
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text
Revision
445.18(A)(B) Generator Disconnect –
Parallel Installations and Location
Change Summary
Revision clarifies the separation of an emergency
shutdown and a disconnecting means.
Article 445 – Generators
445.18 Disconnecting Means.
(A) Disconnecting Means. Generators other than cord-
and-plug-connected portable generators shall have one or
more disconnecting means. Each disconnecting means shall
simultaneously open all associated ungrounded conductors.
Each disconnecting means shall be lockable open in
accordance with 110.25.
The disconnecting means shall be permitted to be located
within the generator behind a hinged cover, door, or
enclosure panel. Where the generator disconnecting means
continued on page 86