Install Instructions

Cat. No. FWP
N° de cat. FWP
No. de cat. FWP
INSTALLATION
Integrated Weather-Resistant Cover and Flanged Inlet/Outlet
Locking and Straight Blade configurations
IP64 and NEMA 3R rated
Suitable for use indoors or outdoors
PK-A3128-10-02-0A
ENGLISH
TO INSTALL
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; UNPLUG CORD OR TURN OFF POWER AT CIRCUIT BREAKER
OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
1. Cut panel opening and run wires through (see Panel Mounting Diagram).
2. Strip cord jacket and individual conductors per appropriate STRIP GUIDE.
3. Place gasket on back side of cover (see Fig. 1 & 2).
4. For CWP Devices: Fully back out terminal screws. Twist strands of conductors tightly together (DO NOT TIN
CONDUCTORS). Insert conductors into proper wire wells as follows: BLACK (Hot) wire to BRASS screw, WHITE
(Neutral) wire to SILVER screw, and GREEN (Ground) wire to GREEN screw (see Fig. 1 & 3). Tighten terminal
screws firmly to 10-14 in.-lbs. CAUTION: TERMINAL CLAMPS MUST TIGHTEN ONTO BARE CONDUCTOR
ONLY, NOT INSULATION.
NOTE: Maximum wire AWG #10 stranded. NOTE: Insert Ground conductor into wire well first for ease of installation.
For FWP Devices: Fully back out terminal screws. Twist strands of conductors tightly together (DO NOT TIN
CONDUCTORS). Securely crimp short fork terminals (not supplied) onto conductors and insert into proper fork
slots as follows: BLACK (Hot) wire to BRASS screw, WHITE (Neutral) wire to SILVER screw, and GREEN (Ground)
wire to GREEN screw (see Fig. 2 & 4). Tighten terminal screws firmly to 10-14 in.-lbs. NOTE: Use Short Fork
Terminals, insulated #12-10, stud size 10, such as AMP
®
Part #52943. NOTE: Maximum fork size: 0.43" (1.09 cm)
wide by 0.06" (0.15 cm) thick. NOTE: Insert Ground fork into fork slot first for ease of installation.
5. Mount device to panel with four (4) screws provided (see Fig. 5 & 6). Torque screws 6 in.-lbs. to 8 in.-lbs. DO NOT
overtighten screws. Ensure that gasket is visible around the edges of the cover to ensure seal.
6. Plug in cord or restore power at circuit breaker or fuse. INSTALLATION IS COMPLETE.
For further information, go to www.leviton.com/industrial
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com© 2016 Leviton Mfg. Co., Inc.
PK-A3128-10-02-0A
LIMITED 10 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship
under normal and proper use for ten years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.
leviton.com or call 1-800-824-3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product
is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in
accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied
warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to ten years. Leviton
is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or
delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the attention of the Quality
Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
WARNING AND CAUTIONS:
TO AVOID FIRE, SHOCK, OR DEATH; UNPLUG CORD OR TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE POWER IS OFF BEFORE WIRING!
TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH ELECTRICAL CODES AND REGULATIONS.
IF YOU ARE UNSURE ABOUT ANY PART OF THESE INSTRUCTIONS, CONTACT AN ELECTRICIAN.
USE THIS DEVICE WITH COPPER OR COPPER CLAD WIRE ONLY.
NOTE:
Refer to NEC article 400 tables (in U.S.A) for proper wire type and size for your application and load.
Strip Guide / Guide de dénudage / Guía de pelado
CWP Devices (for wire terminal) / Dispositifs CWP (bornes à fil)
Productos CWP (para conductor terminal)
FWP Devices (for fork terminal) / Dispositifs FWP (bornes à
fourche) / Para producto FWP (para aleta terminal)
Insulation
Isolant
Aislante
Wire Strands
Brins de cuivre
Hilos del conductor
Cord Jacket
Gaine
Forro del Cordón
9/16" (1.4 cm)
1,4 cm (0,56 po)
1.4 cm (9/16")
15/16" (2.4 cm)
2,4 cm (0,94 po)
2.4 cm
(
15/16"
)
Insulation
Isolant
Aislante
Wire Strands
Brins de cuivre
Hilos del conductor
Cord Jacket
Gaine
Forro del Cordón
7/16" (1.1 cm)
1,1 cm (0,44 po)
1.1 cm (7/16")
15/16" (2.4 cm)
2,4 cm (0,94 po)
2.4 cm
(
15/16"
)
Cat. No. CWP
N° de cat. CWP
No. de cat. CWP
Cat. No. CWP
N° de cat. CWP
No. de cat. CWP
Terminal Screw
Borne à vis
Tornilllo terminal
Terminal Screw
Borne à vis
Tornilllo terminal
Gasket
Joint d’étanchéité
Empaquetadura
Ground Screw
Vis Terre
Tornillo Tierra
Cat. No. FWP
N° de cat. FWP
No. de cat. FWP
Terminal Screw
Borne à vis
Tornilllo terminal
Terminal Screw
Borne à vis
Tornilllo terminal
Gasket
Joint d’étanchéité
Empaquetadura
Ground Screw
Vis Terre
Tornillo Tierra
Note: Tap screw holes for #6 UNC Screw (4 places).
Remarque : tarauder les trous pour des vis à filetage UNC
n° 6 (4 endroits).
Nota: Orificios para tornillos #6 UNC (4 lugares)
Panel Mounting
Installation sur panneau
Panel de Montaje
Fig. 7Fig. 1 Fig. 2
Fig. 3 Fig. 5 Fig. 6Fig. 4
A = 1.9" (4.8 cm)
B = 3.3" (8.4 cm)
C = 2.3" (5.8 cm)
C
A
B
Third party trademarks are the property of their respective owners.