Commercial/Industrial Surge Protective Devices (SPDs) Complete Surge Protection Solutions for Industrial, Commercial and Residential Applications
UL 1449 3rd Edition: Why is this so important? UL 1449 is Underwriters Laboratories’ safety and performance standard for surge protection equipment. In 2009, this Standard was revised to the 3rd Edition. In addition to some nomenclature changes, there were two very important objectives for revising the UL 1449 Standard: to harmonize with the International standards for surge protective equipment (IEC 61643-1) and to modify performance tests to better simulate real world exposure.
Table of Contents UL 1449 3rd Edition: Why is this so important?..............................................2 Surge Protection Network Implementation....................................................4 Type 1 Surge Protective Devices.........................................................................5 50240-MSA, 51120-3R and 55000 Series.................................................................................... 6 Type 2 Surge Protective Devices..............................................
Surge Protection Network In order to achieve optimum protection for your equipment, it is essential to utilize a distributed approach to surge suppression. That is, you’ll need to install surge protective devices (SPDs) that knock down high-energy transients at the building entrance and/or sub-panel so that they’re manageable for the smaller SPDs that protect PCs and other equipment at point-of-use.
Type 1 Surge Protective Devices Permanently connected SPDs intended for installation between the secondary of the service transformer and the line side of the service equipment overcurrent device, as well as the load side, including watt-hour meter socket enclosures and intended to be installed without an external overcurrent protective device. www.leviton.
Type 1 Surge Protective Devices Leviton's Type 1 Surge Protective Devices protect against lightning strikes entering into main service panels or electrical equipment with high exposure to lightning, such as farming irrigation systems. 51120-3R 55208-ASA 55000 Series Surge Protective Devices n Provided with #10 AWG stranded, 18 in.
Specifications for: 55000 Series, 51120-3R and 50240-MSA Surge Protective Devices 55240-ASA 55208-ASA 55480-ASA 51120-3R 50240-MSA 120/240V Single Phase 120/208V 3Ø WYE, 240V 3Ø Delta 277/480V 3Ø WYE, 480V 3Ø Delta 120/240V Single Phase 120/240V Single Phase 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz TPMOV TPMOV TPMOV TPMOV TPMOV — — — — 200A* * Nominal Discharge Rating (IN) 20kA 20kA 20kA 20kA 20kA Maximum Continuous Operating Voltage (MCOV) 150V 150V 320V 150V(L-N)/300V(L-
Dimensions for: 51120-3R, 55000 Series and 50240-MSA Surge Protective Devices 8.00in 203.2mm 51120-3R 6.50in 165.1mm 4.45in 113.0mm FRONT SIDE 6.00in 154.4mm 4.00in 101.6mm 55000 Series 18.00in ) mm (457.2 3.13in (79.4mm) 3.13in (79.4mm) 3.00in (76.2mm) 3.13in (79.4mm) Typical for 50240-MSA 3.7 3.7 2 2 94. in Ref 94. in Ref 5m 5m m m 3.13in 79.4mm 6.6 16 2in 8.3 Ref mm 3.13in 79.4mm 6.6 16 2in 8.3 Ref mm 3.13in 79.4mm 3.13in 79.4mm 3.13in 79.4mm 79.4mm 00in 2mm 6.94in Ref 6.
Type 2 Surge Protective Devices Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device; including SPDs located at the branch panel. www.leviton.
Quick Reference – Type 2 Surge Protective Devices Catalog Number Max Surge Current, Per Mode (Per Phase) Nominal Discharge Current (IN) Replaceable Modules NEMA Enclosure Surge Counter Noise Filtering 120V and 120/240V, Single-Phase 52120-M1 100kA (100kA) 20kA Yes Type 12 No Yes 52120-M2 100kA (100kA) 20kA Yes Type 12 No Yes 52120-CM2 100kA (100kA) 20kA Yes Type 12 Yes Yes 52120-M2H 100kA (100kA) 20kA Yes Type 12 No Yes 32120-1 80kA (80kA) 3kA No Type 3R No Yes 4212
Type 2 Modular Surge Protective Devices Leviton’s 74000 and 75000 Series panel mounted surge protective devices provide seven-mode protection in WYE-configured, 3-phase AC systems. Designed for most industrial and commercial environments with critical operations, these panels offer complete protection at the building entrance and distribution panel.
Specifications and Dimensions for: 74000 / 75000 Series Catalog Number 74120-7M3 74277-7M3 75120-7M3 75277-7M3 120/208 VAC 3-phase WYE 277/480 VAC 3-phase WYE 120/208 VAC 3-phase WYE 277/480 VAC 3-phase WYE 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Surge Technology 40mm MOV 40mm MOV 53mm MOV 53mm MOV Recommended Circuit Breaker Rating 30A, 120V 30A, 277V 30A, 120V 30A, 277V L-L 300V 640V 300V 640V L-N 150V 320V 150V 320V L-G 150V 320V 150V 320V N-G 150V 320V 150V 320V L-
Type 2 Modular Surge Protective Devices Leviton’s 52000 and 57000 Series panel mounted surge protective devices provide a good mix of value, performance, and features for main service or branch panel applications in industrial, commercial and residential environments. The paralleloperated design ensures continuous power even if surge protection is disabled.
Ordering Information Description Voltage (V AC) Configuration Max Surge Current, Per Mode (Per Phase) Replacement Modules 52120-M1 2-Mode Surge Protection Panel 120 Single-phase, 2-wire + gnd 100kA (100kA) (1) 2120, (1) 8120-GN 52120-M2 3-Mode Surge Protection Panel 120/240 Single-phase, 3-wire + gnd 100kA (100kA) (2) 2120, (1) 8120-GN 52120-CM2 3-Mode Surge Protection Panel, with Surge Event Counter 120/240 Single-phase, 3-wire + gnd 100kA (100kA) (2) 2120, (1) 8120-GN 52120-M2H 3-Mode
Specifications for: 57000 Series 57120-M3 57120-CM3 57240-DM3 57277-M3 57277-CM3 57480-DM3 57347-M3 57600-DM3 120/208VAC 3-phase WYE 240VAC 3-phase Delta 277/480VAC 3-phase WYE 480VAC 3-phase Delta 347/600VAC 3-phase WYE 600VAC 3-phase Delta 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Surge Technology 40mm MOV 40mm MOV 40mm MOV 40mm MOV 40mm MOV 40mm MOV Recommended Circuit Breaker Rating 30A, 120V 30A, 240V 30A, 277V 30A, 480V 30A, 600V 30A, 600V Nominal Discharge
Specifications for: 52000 Series Catalog Number 52120-M1 52120-M2 52120-CM2 52120-M2H 52120-M3 52120-CM3 52120-7M3 52120-7C3 52120-7MS 52120-7CS 52240-DM3 52277-M3 52277-CM3 52277-7M3 52277-7C3 52277-7MS 52277-7CS 52480-DM3 52412-DS3 120/ 240VAC 120/ 240VAC 120/ 208VAC 3-phase WYE 120/ 208VAC 3-phase WYE 240VAC 3-phase Delta 277/ 480VAC 3-phase WYE 277/ 480VAC 3-phase WYE 480VAC 3-phase Delta 120/240/ 120VAC 3-phase Hi-Leg Delta Electrical Specifications Voltage 120VAC Frequency 50/60
Type 2 Non-Modular Surge Protective Devices Leviton’s 37000 and 47000 Series panel mounted surge protective devices provide seven-mode protection in WYE-configured, 3-phase AC systems. These devices are designed for installation at the service entrance, at branch panels, or as dedicated transient surge protection for critical equipment.
Specifications and Dimensions for: 37000 and 47000 Series Catalog Number 37120-7 37277-7 47120-7 47120-4X7 47277-7 47277-4X7 120/208 VAC 3-phase WYE 277/480 VAC 3-phase WYE 120/208 VAC 3-phase WYE 120/208 VAC 3-phase WYE 277/480 VAC 3-phase WYE 277/480 VAC 3-phase WYE Electrical Specifications Voltage Frequency Surge Technology Recommended Circuit Breaker Rating 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 40mm MOV 40mm MOV 40mm MOV 40mm MOV 40mm MOV 40mm MOV 30A, 120/208V 30A,
Type 2 Non-Modular Surge Protective Devices One of our most popular series, Leviton’s 32000 and 42000 surge protection panels provide protection for up to 80kA of surge current per mode. They feature noise filtering, visual and audible indication of surge protection status and dry contacts for remote monitoring, all in a compact enclosure.
Type 2 Surge Protective Devices Leviton’s 51120 Series panel mount surge protective devices are designed for use in homes and apartment buildings at the service entrance, electrical utility meter, or other branch panel locations. They are also ideal for use in pumping stations, radio towers and light commercial buildings where protection from high-energy, high-voltage transients is desired.
Specifications for: 32000/42000, 51120-1 and 51120-3 51120-1 51120-3 32120-1 42120-1 32120-DY3 42120-DY3 32277-DY3 42277-DY3 32412-DS3 42412-DS3 32347-DY3 42347-DY3 120/240V AC, Single-Phase 120/208V AC, 3-Phase WYE 120V/240V Single Phase 120V/208V 3Ø WYE, 208V 3Ø Delta, 220V 3Ø Delta 277V/480V 3Ø WYE, 220V/380V 3Ø WYE, 240V 3Ø Delta, 480V 3Ø Delta 120V/240V/120V 3Ø Hi-leg Delta 347V/600V 3Ø WYE, 600V 3Ø Delta 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 40mm MOV 40mm MOV 4
FRONT 7.50in 190.5mm SIDE 2.25in 57.1mm 2.25in 1.00in 57.1mm 2.00in 25.4mm 1.15in 1.00in 29.3mm 50.9mm 25.4mm TOP TOP 3.25in 3.25in 82.5mm 82.5mm 3.25in 82.5mm 5.25in 5.25in 133.4mm 133.4mm 4.81in 4.81in 122.2mm 122.2mm 6.00in 152.4mm 6.00in 152.4mm 3.50in 88.9mm 3.50in 88.9mm 7.00in 7.00in 177.8mm 177.8mm 42001-FMC 4.25in 4.25in 4.31in 107.9mm 107.9mm 109.4mm SIDE 6.25in 6.25in 158.7mm 158.7mm 6.31in 8.25in 8.25in 160.2mm 209.5 209.5 mm mm8.40in 213.3mm FRONT 6.75in 171.4mm 6.25in 6.
Type 2 Surge Protective Devices Leviton's 51110 Series Residential Surge Protection Panels are designed for mounting at the service entrance in homes, apartments and condominiums. They offer advanced surge protection for modern electronics and appliances, reducing the risk of damage from spikes and surges entering the property through AC power lines.
Specifications for: 51110 Series Catalog Number 51110-SRG Electrical Specifications Voltage 120/240V AC, Single-Phase Frequency 50/60Hz Surge Technology MOV Recommended Circuit Breaker Rating 30A, 120/240V Performance Data Nominal Discharge Rating (IN) 3kA L-N 150V L-G 150V N-G 150V L-L 300V Maximum Continuous Operating Voltage (MCOV) Maximum Surge Current, Per Mode (Per Phase) 48kA (96kA) Short Circuit Current Rating 10kA Diagnostics Voltage Protection Rating (VPR) Protection sta
Type 3 Surge Protective Devices Point of utilization SPDs, installed at a minimum conductor length of 10 meters (30 feet) from the electrical service panel to the point of utilization. For example cord connected, direct plug-in, receptacle type and SPDs installed at the utilization equipment being protected. The distance (10 meters) is exclusive of conductors provided with or used to attach SPDs. www.leviton.
Type 3 Surge Protective Devices Leviton offers the broadest selection of surge protective receptacles in the industry. The low cost of these receptacles, combined with their ease of installation, means they can be placed anywhere you have a standard electrical outlet. So with a small investment, you have the assurance that your equipment is well protected, whether it’s a heart monitor in the emergency room, a computer in your office, or the big screen TV in your living room.
Ordering Information Commercial / Industrial Grade Decora® TR Surge Protective Receptacles Color Amp. Outlet Configuration Brown Ivory White Gray Red Blue Black Orange Lt.
Specifications and Dimensions for: Surge Protective Receptacles Common to Tamper-Resistant Receptacles Electrical Specifications Dielectric Voltage Withstands 2000V per UL498 Current Limiting Full Rated Current Temperature Rise Max 30C after 250 cycles OL at 200% rated current 2.72in 2.72in 2.72in 69.1mm69.1mm 69.1mm 3.81in 3.81in 3.81in 96.8mm96.8mm 96.8mm 4.21in 4.21in 4.21in 106.9mm 106.9mm 106.
Type 3 Surge Protective Devices Leviton’s family of medical grade power strips are designed explicitly for use in health care facilities, including patient care areas as defined by NEC (2011) Article 517. These devices also satisfy electrical safety requirements specified in NFPA 99 (2012): Health Care Facilities Code, allowing facility managers to ensure that their facilities are compliant with this safety regulation.
Specifications and Dimensions for: Medical Grade Power Strips Medical Grade Power Strips Surge Protective Medical Grade Power Strips 5302M-1N7 5304M-1N7 5306M-1N7 5302M-1N5 5304M-1N5 5306M-1N5 5302M-2N7 5304M-2N7 5306M-2N7 5302M-2N5 5304M-2N5 5306M-2N5 Current 15A (12A max continuous load) 20A (16A max continuous load) Voltage 125V Frequency 60Hz Catalog Number 5302M-1S7 5304M-1S7 5306M-1S7 5302M-1S5 5304M-1S5 5306M-1S5 5302M-2S7 5304M-2S7 5306M-2S7 5302M-2S5 5304M-2S5 5306M-2S5 Current 15A (1
Type 3 Surge Protective Devices Leviton’s 5100 and 5300 Series surge protected power strips offer superior protection for any Commercial, Industrial, or Hospital application. Our Industrial strips feature robust construction, including durable metal housings while our Commercial Grade strips feature a durable thermoplastic housing. They are available in two performance levels to address surge protection needs in a variety of commercial and industrial environments.
Specifications and Dimensions for: 5100 & 5300 Series Surge Strips Catalog Number 5100-IPS 5100-IS2 Series 5300-IPS 5300-H15 5300-HTS 5300-HT2 5100-PS 5100-S15 Industrial/Hospital 5300-PS 5300-S15 Commercial Electrical Specifications Voltage 125VAC 125VAC 125VAC 125VAC 125VAC 125VAC 125VAC 125VAC Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz Surge Technology MOV MOV MOV MOV MOV MOV MOV MOV Current 15A 20A 15A 15A 15A 20A 15A 15A Max
Type 3 Surge Protective Devices Leviton’s S1000 and S2000 Series Surge Protected Strips provide superior protection for everyday use in professional work areas and home offices, protecting computers, peripherals and other electronic devices from damaging surges, voltage transients and noise spikes.
Specifications and Dimensions for: S1000 & S2000 Series Surge Strips Catalog Number S1000-PS, S1000-S15, S1000-PTC S2000-PS, S2000-S15, S2000-PTC Electrical Specifications Voltage 120V 120V 50/60 Hz 50/60 Hz Surge Technology MOV MOV Amperage 15A 15A Maximum Continuous Operating Voltage (MCOV) 150V 150V Maximum Surge Current, Per Mode (L-N) 25kA 62.
Type 3 Surge Protective Devices Leviton’s Plug-In Surge units plug directly into a standard wall outlet to provide surge protection for up to six devices. They are ideal for immediate surge protection in tight spaces such as behind desks, book cases, sofas, and media equipment.
Specifications and Dimensions for: 3500 Series Wall-Mount Surge Protectors Catalog Number 3500-P 3500-PC 3500-PT Electrical Specifications Voltage 120V 120V 120V 50/60Hz 50/60Hz 50/60Hz Surge Technology MOV MOV MOV Current 15A 15A 15A Maximum Continuous Operating Voltage (MCOV) 130V 130V 130V Maximum Surge Current, Per Mode 36kA 36kA 36kA -10 to -45dB (@50KHz to 100MHz) -10 to -45dB (@50KHz to 100MHz) -10 to -45dB (@50KHz to 100MHz) 600V 600V 600V Frequency Performance Data
Type 4 Surge Protective Devices Component Assemblies - Component assembly consisting of one or more Type 5 components — discrete component surge suppressors, such as MOVs that may be mounted on a PWB, connected by its leads or provided within an enclosure with mounting means and wiring terminations — together with a disconnect (integral or external). www.leviton.
Type 4 Surge Protective Devices Leviton’s 51000 Series Surge Protective Devices provide point-of-use surge protection for industrial applications such as factory automation servo motors, drives and PLCs. Available in models with maximum load currents of 5 to 16 amps and in both wall-mounted and DIN rail mounted configurations. 51020-DIN 51000 Series UL Recognized Components n Protection for up to 52,000 amps of surge current per mode n Tested to ANSI/IEEE C62.41 and C62.
Type 4 Surge Protective Devices Leviton’s 3800 Series surge protective devices are designed to provide wired-in surge protection for devices in industrial and commercial equipment cabinets. These devices are suitable for 125V AC applications. Available in standard equipment or DIN rail mount with terminal block for connections, or standard equipment mount with 6" long wire leads for termination and remote LED.
Specifications for: 3800 & 51000 Series 51005-DIN 51005-WM 51010-DIN 51010-WM 51015-WM 51020-DIN 51020-WM 51240-DIN 51240-WM 3800-DIN 3800-WM 3800-OEM 120VAC 120VAC 120VAC 120VAC 240VAC 125V AC 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz MOV MOV MOV MOV MOV MOV 5 Amp 10 Amp 15 Amp 16 Amp 16 Amp N/A Nominal Discharge Current (IN) N/A N/A N/A N/A N/A 3kA Maximum Continuous Operating Voltage (MCOV) 150V 150V 150V 150V 270V 130V Maximum Surge Current, Per Ph
Catalog Number 3800-WM DIN RAIL CLIP 2.69in 68.3mm 3.28in 83.3mm 3.78in 96.0mm 1.66in 42.2mm .83in 21.8mm 2.69in 68.3mm 3.28in 83.3mm 3.78in 96.0mm 6.90in 175.3mm .85in 21.6mm 1.25in 31.8mm .70in TYP 17.8mm 5.10in 129.5mm 7.50in 1.41in 35.8mm 2.71in 68.8mm 2.71in 68.8mm .73in 18.5mm 190.5mm Catalog Number 51020-WM Catalog Number 3800-DIN 1.41in 35.8mm .70in TYP 17.8mm .63in 16.0mm 1.25in 31.8mm 2.53in 64.3mm in .19 m m 8 . 4 .70in TYP 17.8mm 5.21in 132.3mm 2.53in 64.3mm in .19 m m 4.8 .
DIN Rail Mount Receptacles The DIN Rail Series provide mounting in equipment cabinets where convenient plug-in surge protection is needed. Available in 120V single and duplex outlet configurations.
Low-Voltage (DC) Surge Protection Modules www.leviton.
Low Voltage (DC) Power Surge Protective Modules Leviton’s 3800 Series DC surge protective devices are designed for mounting in standard equipment cabinets where surge suppression is desired for the enclosed equipment. Compact black-box styling coordinates with other mounted equipment. The MOV-based suppression circuitry provides optimum clamping. Available in standard equipment mount and DIN-rail mount configurations.
Dimensions and Specifications for: 3800 Low Voltage Power Series 3824-DIN 3824-WM Maximum DC Operating Voltage 13.2VDC 26.4VDC Breakdown Voltage 100V/µsec 14.7 – 19.8 V 33.1 – 38.2 V Maximum Surge Current 10 x 1000µsec 10A 10A Maximum Capacitance 4.8µf 4.8µf UL497B Clamping 21V 37V 3848-DIN 3848-WM 3838-OEM" .85in 21.6mm 4.8µf Material Specifications .85in 21.6mm Environmental Specifications Polycarbonate -10ºC to 60ºC Altitude 20% - 90% non-condensing 2.69in 68.3mm 3.28in 83.3mm 3.
Low-Voltage (DC) Data Line Surge Protective Modules Leviton’s 3400/3800 Series surge protective modules are designed to provide applicationspecific surge protection for factory automation and industrial control devices. They are available in various DC voltage configurations, connection types and mounting styles.
Specifications for: 3400/3800 Series Low Voltage Data Line Surge Protection Modules Catalog Number 3420-9 3420-35 3803-485 3803-DHP 3803-MOD 3860-GEF 3861-ETH 3862-CON 3863-DEV (-)4.5 to 4.5 30VDC (V+ to G) (-)4.5 to 4.5 (-)4.5 to 4.5 (-)4.5 to 4.5 100.4VDC (L-G) 16.4VDC (L-Shield) 19.8VDC (L-G) 5.6VDC (L-L) 9.18VDC (L-G) 9.18VDC (L-Shield) 19.8VDC (L-G) 5.6VDC (L-L) Clamping Voltage 12Vpk 48Vpk 12Vpk 12Vpk 12Vpk 205.4Vpk (L-G) 60.7Vpk (L-Shield) 119Vpk (L-G) 56Vpk (L-L) 62.
Dimensions for: 3400/3800 Series Surge Protection Modules 1.70in 43.2mm Catalog Number 3860-GEF ¼in 6.00in± m m±6.4m 152.4m 1.70in 43.2mm 1.70in 43.2mm 3.00in 76.2mm 1. 38 51in .3m m 1 0in 6.0 .4mm 2 15 Catalog Number n 3803-485 6.00i mm 1. 38 51in .3m m 1. 38 51in .3m m 0in 6.0 .4mm 2 15 3.00in 76.2mm 3.00in 76.2mm .79in 20.1mm 6in 2.2 mm .4 7 5 6in 2.2 mm .4 7 5 .79in 20.1mm 2.4 1. 38 51in .3m m 0in 6.0 .4mm 2 15 1.70in 43.2mm 3.00in 76.2mm 1. 38 51in .3m m 15 6in 2.2 mm .
Technical Reference Materials www.leviton.
Applicable Codes & Standards Regarding Medical Grade Power Strips What is a Medical Grade Power Strip? It is a power strip for use with medical equipment and with medical approval under the UL guidelines. They are intended for use inside Patient Care Areas and specifically within the 6 foot perimeter of the patient, known as the Patient Care Vicinity.
Patient Care Areas: As defined in NFPA 99 – 2012 Edition Patient Care Vicinity (Illustrated below) A space, within a location intended for examination and treatment of patients, extending 6 feet (1.8 m) beyond the normal location of the bed, chair, table, treadmill, or other device that supports the patient during examination and treatment and extending vertically 7.5 feet (2.3 m) above the floor. 7.
Accurate Assessment of Electrical Systems Accurate Assessment of Electrical Systems Precise identification of the electrical system is critical in the proper selection and application of the most effective surge protective device. Since SPD performance is directly related to nominal line-voltage parameters, line voltage measurements should always be taken by a qualified electrician before the SPDs are specified and installed.
Glossary Clamping Voltage (Also known as Let-Through Voltage) The voltage at which a surge suppressor performs its suppression tasks such as diverting (shunt) the surge from line to ground or absorbing the excessive energy. Common Mode When relating to SPDs, common mode refers to surge protection components provided between L-G and N-G modes. Maximum Continuous Operating Voltage (MCOV) The maximum voltage that can be continuously applied to each mode of the SPD without degradation.
Product Warranties Leviton Surge Protective Device product warranties are summarized in Table 1. For a select group of products, Leviton also provides connected equipment coverage via a “True Whole House Surge Protection” Limited Warranty. The details are summarized in Table 2.
Whole House Surge Protection The Good, Better, Best Approach to “Whole House” Surge Protection Good Better Best Surge Protective Plug-Ins or Strips to plug your tablet, refrigerator, or even your HDTV into. Surge Protective Plug-Ins or Strips AND a Surge Protective Panel that protects your main electrical panel.
Leviton Manufacturing Co., Inc. 201 N Service Rd, Melville, NY 11747 Telephone: 1-800-323-8920 • Fax: 1-800-832-9538 Tech Line (8:30AM-7:00PM E.S.T. Monday-Friday): 1-800-824-3005 Leviton Manufacturing of Canada, Ltd. 165 Hymus Blvd, Pointe-Claire, QC H9R 1E9 Telephone: 1-800-469-7890 • Fax: 1-800-563-1853 Leviton S. de R.L. de C.V. Lago Tana 43, Col. Huichapan, Miguel Hidalgo, CP 11290 México DF Telephone: (+52) 55-5082-1040 • Fax: (+52) 55-5386-1797 • www.leviton.com.mx Visit our Website at: www.