Instructions / Assembly

INTRODUCTION
Transient voltage surges are short-term deviations from a desired voltage level or signal that can occur at any time. Such changes can result in an electronic
device malfunction, or cause extensive damage. Also termed "spikes", these occurrences take place as a result of magnetic field/inductive coupling or
whenever the line current is interrupted. They can originate from either inside a facility, or derive from outside utility lines. Sources within a facility involve loads
that are switched, such as electric motors that are turned ON and OFF and are addressed by devices applied at point-of-use equipment.
DESCRIPTION
Leviton's 55240-ASA, 55208-ASA, and 55480-ASA are the first line of protection designed to safeguard homes and small commercial establishments from
external sources of high voltage spikes. These TYPE 1 devices are connected between each of the two incoming Lines and Neutral.
SPECIFICATIONS
ETL listed TYPE 1 device.
Suppression in accordance with recommendations of ANCI/IEEE C62.11 and NEC 285.
40mm TPMOV fused SPD circuitry for all lines to Neutral.
SPD enclosed in NEMA type 3R case for outdoor installation.
Alarm is activated whenever either line loses surge protection.
Green LED indicates surge protection is stable.
Red LED indicates protection has failed.
LOCATION AND MOUNTING
1. Locate the SPD between the meter and the main service circuit breaker panel or connect at weather head of overhead service.
2. Mount the SPD so the Line and Neutral connections can be made while keeping hook-up leads as short and straight as possible. Avoid sharp bends and
turns, which will degrade the performance of the SPD. The weight of the SPD should be supported to avoid unnecessary stress on the wiring connections.
3. The SPD should be mounted to an electrical box or enclosure. DO NOT connect directly to electrical conduit.
TO INSTALL
IMPORTANT: TYPE 1 SPD devices should be supplemented with additional load side SPDs for maximum protection.
1. RESTORE POWER, if necessary.
2. Measure voltage at installation location between each Line and Neutral. System voltage must not exceed the specified maximum continuous RMS voltage
listed on the SPD label.
3. TURN OFF POWER at the installation location (usually by removing service to meter or disconnection of service supply by utility).
4. Switch all distribution panel circuit breakers to OFF position to reduce possibility of accidental voltage on the circuit.
5. Connect the SPD White (Neutral) wire to the Neutral service conductor, a grounding electrode conductor, or the equipment grounding terminal in the
service equipment.
For Cat. No. 55240-ASA: Connect Line 1 to one of the SPD's Black wires and Line 2 to the remaining Black wire. Refer to Figure 1.
For Cat. No. 55208-ASA & 55480-ASA: Connect Line 1 to one of the SPD's Black wires, connect Line 2 to one of the remaining Black wires and Line 3 to
the remaining Black wire. Refer to Fig. 2.
NOTE: Keep hook-up leads as short and straight as possible.
6. Restore power to SPD and switch circuit breakers to "ON" position to reconnect load. Verify that the Green LED is lit. INSTALLATION IS COMPLETE.
If Green LED is not lit and instead Red LED is lit, then re-check installation. Replace unit as required.
INSTALLATION ENGLISH
PK-93718-10-02-0A
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
SURGE PROTECTIVE DEVICE (SPD)
Cat. No. 55240-ASA: Single Phase 120/240V AC, 50/60Hz
Cat. No. 55208-ASA: 3 Phase 120/208V AC WYE, 50/60Hz or 240V AC Delta, 50/60Hz
Cat. No. 55480-ASA: 3 Phase 277/480V AC WYE, 50/60Hz or 480V AC Delta, 50/60Hz
Fig. 1 - 55240-ASA
Incoming Power
Alimentation
Entrada de Energía
Line 1 (Black)
Ligne 1 (Noir)
Línea 1 (Negro)
Line 2 (Black)
Ligne 2 (Noir)
Línea 2 (Negro)
Line 1
Ligne 1
Línea 1
Line 2
Ligne 2
Línea 2
Neutral
Neutre
Neutro
Neutral (White)
Neutre (Blanc)
Neutro (Blanco)
TYPE 1 SPD
120/240V AC
DLS de TYPE 1
120/240 V c.a.
TIPO 1 PST
120/240V CA
Alternate Connection
of Grounding Electrode
Raccord optionnel de
l’électrode de mise à la masse
Conexión Alterna
del Electrodo a Tierra
Line 1 (Black)
Ligne 1 (Noir)
Línea 1 (Negro)
Line 2 (Black)
Ligne 2 (Noir)
Línea 2 (Negro)
Neutral (White)
Neutre (Blanc)
Neutro (Blanco)
TYPE 1 SPD
120/240V AC
DLS de TYPE 1
120/240 V c.a.
TIPO 1 PST
120/240V CA
Circuit Breaker Panel
Panneau à disjoncteurs
Panel Interruptor de Circuito
Preferred Location
Emplacement préférable
Ubicación Preferencials
Alternate Location
Emplacement optionnel
Ubicación Preferencials
Metering (Instrument or Self-Contained)
Compteur (instrument ou autonome)
Medidor (Instrumento o Auto-Contenido)
Fig. 2 - 55208-ASA, 55480-ASA
Incoming Power
Alimentation
Entrada de Energía
Line 1 (Black)
Ligne 1 (Noir)
Línea 1 (Negro)
Line 2 (Black)
Ligne 2 (Noir)
Línea 2 (Negro)
Line 1
Ligne 1
Línea 1
Line 2
Ligne 2
Línea 2
Line 3
Ligne 3
Línea 3
Neutral
Neutre
Neutro
Neutral (White)
Neutre (Blanc)
Neutro (Blanco)
Alternate Connection
of Grounding Electrode
Raccord optionnel de
l’électrode de mise à la masse
Conexión Alterna
del Electrodo a Tierra
Line 3 (Black)
Ligne 3 (Noir)
Línea 3 (Negro)
Circuit Breaker Panel
Panneau à disjoncteurs
Panel Interruptor de Circuito
Preferred Location
Emplacement préférable
Ubicación Preferencials
Line 1 (Black)
Ligne 1 (Noir)
Línea 1 (Negro)
Line 2 (Black)
Ligne 2 (Noir)
Línea 2 (Negro)
Neutral (White)
Neutre (Blanc)
Neutro (Blanco)
Line 3 (Black)
Ligne 3 (Noir)
Línea 3 (Negro)
Alternate Location
Emplacement optionnel
Ubicación Preferencials
Metering (Instrument or Self-Contained)
Compteur (instrument ou autonome)
Medidor (Instrumento o Auto-Contenido)
TYPE 1 SPD
55208-ASA: 3 Phase
120/208V AC WYE
or 240V AC Delta
55480-ASA: 3 Phase
277/480V AC WYE
or 480V AC Delta
PST TIPO 1
55208-ASA: Trifásico
120/208V AC WYE o
240V AC Delta
55480-ASA: Trifásico
277/480V AC WYE o
480V AC Delta
LST DE TYPE 1
55208-ASA : triphasé,
120/208 V c.a. en étoile
ou 240 V c.a. en triangle
55480-ASA : triphasé,
277/480 V c.a. en étoile
ou 480 V c.a. en triangle
TYPE 1 SPD
55208-ASA: 3 Phase
120/208V AC WYE
or 240V AC Delta
55480-ASA: 3 Phase
277/480V AC WYE
or 480V AC Delta
PST TIPO 1
55208-ASA: Trifásico
120/208V AC WYE o
240V AC Delta
55480-ASA: Trifásico
277/480V AC WYE o
480V AC Delta
LST DE TYPE 1
55208-ASA : triphasé,
120/208 V c.a. en étoile
ou 240 V c.a. en triangle
55480-ASA : triphasé,
277/480 V c.a. en étoile
ou 480 V c.a. en triangle
WARNING AND CAUTIONS:
TO BE INSTALLED AND/OR USED IN ACCORDANCE WITH APPROPRIATE ELECTRICAL
CODES AND REGULATIONS
INSTALLATION OF TYPE 1 SPDs DEVICES MUST BE PERFORMED BY AN ELECTRICIAN.
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER BY REMOVING SERVICE METER,
OR DISCONNECTION OF SERVICE SUPPLY BY UTILITY. TEST THAT THE POWER IS OFF
BEFORE WIRING!
THIS SPD IS A TYPE 1 DEVICE WHICH IS DESIGNED FOR USE
WITH LIGHTNING PROTECTION SYSTEMS (UL 96A).
THIS SPD MAY NOT SURVIVE SUSTAINED OVERVOLTAGES.
USE THIS DEVICE WITH COPPER OR COPPER CLAD WIRE ONLY.
THESE DEVICES ARE NOT TO BE USED WITH A HI-LEG DELTA
VOLTAGE CONFIGURATION.
LIMITED LIFETIME WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal
and proper use during the lifetime of the product. Leviton’s only obligation is to correct such defects by repair or replacement, at its option, if the product is returned prepaid, with proof of purchase
date, and a description of the problem to Leviton Manufacturing Co., Inc., Att: Quality Assurance Department, 201 North Service Road, Melville, N.Y. 11747. This warranty excludes and there
is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened,
abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including
merchantability and fitness for a particular purpose. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment,
lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

Summary of content (2 pages)