FAQ

60
Revision/New
305 General Requirements – Systems
Over 1000V ac/1500V dc
Leviton Comment: Article 305 is covered with Article
245 on page 57.
Revision/New
310.3(A)(B) Reconditioned Equipment
Leviton Comment: Article 310.3(A)(B) is covered with
Article 210.23(A) found on page 26.
Revision/New
312.10, 314.5 Screws Protruding into
Boxes – How Much is Allowable
Leviton Comment: We are covering Articles 312.10
and 314.5 together because they are very similar, and
both relate to screws protruding into boxes.
Change Summary
• The NEC has set limits on how far screws can protrude
into boxes.
Article 312 – Cabinets, Cutout Boxes, and Meter Socket
Enclosures
312.10 Screws or Other Fasteners. Screws or other
fasteners installed in the eld that enter wiring spaces shall
be as provided by or as specied by the manufacturer or
shall comply with the following as applicable:
(1) Screws shall be machine type with blunt ends.
(2) Other fasteners shall have blunt ends.
(3) Screws or other fasteners shall extend into the enclosure
no more than 6 mm (1⁄4 in.) unless the end is protected with
an approved means.
Exception to (3): Screws or other fasteners shall be permitted to extend into
the enclosure not more than 11 mm (7⁄16 in.) if located within 10 mm (3⁄8 in.)
of an enclosure wall.
Article 314 – Outlet, Device, Pull, and Junction Boxes;
Conduit Bodies; Fittings and Handhole Enclosures
314.5 Screws or Other Fasteners. Screws or other fasteners
installed in the eld that enter wiring spaces shall be as
provided by or specied by the manufacturer or shall
Material taken from the National Electric Code
®
is reprinted with permission
from NFPA 70
®
, 2023 edition. National Electrical Code
®
, Copyright 2022,
National Fire Protection Association, Quincy, MA. All rights reserved.
NEC
®
Text