Instructions / Assembly

Leviton Manufacturing, Inc.
Lighting Managment Systems Division
20497 SW Teton, Tualatin, Oregon, 97062
800.736.6682 - Customer Service
800.959.6004 - Technical Support
Installation Instructions
Dimensions 4000 series architectural controller
Applies to models: D4104, D4106, D4200, D4206, & D4006
Revision B, April 2008
# PK-93425-10-00-0B
Items required for installation
1. Suitable Backbox
• Preferred 4 gang ‘Gang Box’, Raco #943
Leviton P/N BBG04-000
• 5 gang device backbox
2. Appropriate backbox device plate
• Raised cover for 4 gang gang box
Leviton P/N WPG04-00R
• 4 gang reducer “mud ring” for 5 gang device backbox
3.
D4006, D4104, D4106, D4206 D4200
• Input power (see specs)
• Output to loads
• Optional Luma-Net network
connection
• Luma-Net network connec-
tion
General Installation Steps
1. Read all installation instructions and plan entire system
2. Determine location for device and install the appropriate backbox
D4006, D4104, D4106, D4206 D4200
3. Connect input power.
4. Connect power to loads.
5. Make connections to net-
work (if applicable.)
6. Inspect wiring.
7. Install device in wall.
8. Power up and test system.
9. Confi gure.
3. Make network connections.
4. Inspect wiring.
5. Install device in wall.
6. Power up & test system.
7. Confi gure.
SPECIFICATIONS
Power Input
(D4200 N/A)
120VAC 60hz,
10% tolerance
230VAC 50/60hz,
10% tolerance
Power Output
(D4200 N/A)
• 1000 Watts max per zone,
minimum load 15W per zone
• 1200 Watts max per side
• 1920 Watts max per device
• 800 Watts max per zone,
minimum load 15W per zone
• 1200 Watts max per side
• 2400 Watts max per device
Supported load
Types
(D4200 N/A)
• Incandescent
• Tungsten
• Magnetic Low Voltage
• 2-Wire Fluorescent (Advance Mark 10, Lutron Tu-Wire)
• Electronic Low Voltage when rated for use with forward
phase dimmers
• Neon / Cold Cathode
• Non-dim loads
Listings &
Certifi cations
• UL/cUL
• California Title 24
• FCC Part 15, Class A
Not for use in North America
Environmental
0°-40°C
<= 90% non-condensing humidity
Clock Accuracy to +/- 15 seconds per week
Astro Clock accurate to with 15 minutes
Memory Lifetime memory of confi guration and recorded memories.
Clock maintained for up to 10 days in the event of power
failures
Power Input
Installation Steps:
1. Connection to dedicated input power circuit recommended.
2. Confi rm input circuit has enough available power for
controller plus all connected loads.
3. Connect line, neutral, and ground to terminals as indicated.
Notes:
1. Use Copper Wire only
2. Max (2) #12AWG per terminal
3. Tighten terminals to 9in-lbs torque
4. 75° min insulation temperature rating
5. Remove 3/8” insulation from each circuit conductor
Earth Ground
Input ‘Hot’
Input ‘Neutral’
Auxilary Input
Signal/control
input from
occupancy
sensor or
switch
+24Vdc
power to
Occupancy
Sensor
Notes:
1. When using low voltage wire with a rating of less
than 600V, insulate with the included shrink tube
sleeve.
2. Occ terminal requires +V to signal lock/occ
mode.
3. Available power for all peripherals can not exceed
300mh.
2. Use Copper Wire only
3. Terminals accept #30-12AWG
4. Tighten terminals to 7in-lbs torque
5. 75° min insulation temperature rating
5. Remove 3/8” insulation from each conductor.
Background:
Some models allow an external input which can
trigger scene and/or device lockout. This can
be used when it is desired to lockout a device
by keyswitch, preventing access from the front
panel, or when an Occupancy Sensor is used to
turn on the lights.
Installation Steps:
1. Connect +V/COM terminals to the power in-
put of the signal device.
2. Output from the signalling device shall be
connected to the OCC terminal.
Luma-Net Network
Background:
The Luma-Net network is used for entry stations, partition control/room combine stations, dimmer cabinets, relay cabinets, and
other devices which may be required.
Installation Steps:
1. Connect all wires as shown. Observe all notes, instructions, and low voltage digital network data cable installation best practices.
2. If necessary, install termination jumper. Termination is required only at both ends of the run. DO NOT terminate mid-point
devices.
Notes:
1. Luma-Net networks require a daisy chain topology
2. Use Belden #1502R or #1502P for inter-connection of devices. Belden #9829, #9729, & #88102 are also supported wire types,
however, an addition pair of (2) #18AWG wires is required.
3. A maximum run length of 2000 feet is supported on the data pair.
4. Torque terminals to 7in-lbs.
5. 75° min insulation temperature rating.
6. Remove 3/8” insulation from each circuit conductor.
7. Only 1 power supply is allowed on any network segment. If other power supplies are already supplying power to the network
segment, do not connect +V between sources. Consult factory if unsure as to the proper power routing or connections for the
network.
8. Terminals support 30-12AWG stranded wire.
Lock - (OPTIONAL) - Allows for
dry contact (connection between
common/lock) to initiate lock mode.
This can be used for connection to
an external signaling device which
triggers a scene and if enabled, locks
the device. Unlike the Occ/Lock
input however, this input reuqires a
connection to common, an ‘Active
Low’ signal, to trigger the input.
Termination - Required use on fi rst & last
device on run. See more info to right under
“Digital netwowrk termination”.
To terminate any D4200 device, install a short
piece of wire, aka ‘termination jumper’ between
the terminals labeled TERM & REM-
D4200 CONTROL STATION
PRESET SELECT STATION
C
12
18
15
16
17
13
14
6
9
10
11
7
8
3
4
5
1
2
A
B
DMX
CANCEL
LUMANE
T
CLEAR
PHASE LOSS
AUXILIAR
Y
FULL BRIGHT
COMMUNICATION PORTS
FAN
SAVE
FULL
SELEC
T
BRIGHT
A2000-D
Ground Shield
at one point only!
Terminate L
umaNet in
these locations








+V/COM - for D4200 model only,
this device is the power input. On
all other models, these connections
are a power supply output to other
devices.
Rem+/Rem- - Data connection
Belden 1502
Rem + = Blue
Rem - = White
Belden 1502
+V = Red
Com = Black
Belden 9829
Rem + = Blue/White
Rem - = White/Blue
Belden 9729
Rem + = Red
Rem - = Black
2
APPLIES TO:
D4006
D4104
D4106
D4206
N/A D4200
5
APPLIES TO:
N/A D4006
D4104
D4106
D4206
D4200
Line Voltage Load Termination
Install Steps:
1. Confi rm that the load (watts) is within the specifi cations for your model as
shown in the specifi cation chart.
2. Confi rm that the load type is supported. Load types can be found in the
specifi cation chart.
3. Identify the terminal to which you need to connect the load, strip the wire
as appropriate, and install to the appropriate load terminal.
To load
for Zone 2
Notes:
1. Use Copper Wire only.
2. Max (2) #12AWG per terminal.
3. Torque terminals to 9in-lbs.
4. 75° min insulation temperature rating.
5. Remove 3/8” insulation from each circuit
conductor.
6. The number of outputs on a specifi c
model may differ from that shown.
3
APPLIES TO:
D4006
D4104
D4106
D4206
N/A D4200
4
APPLIES TO:
D4006
D4104
D4106
D4206
D4200
1
APPLIES TO:
D4006
D4104
D4106
D4206
D4200
4 GANG BOX (4-1/2" WIDE X 2-1/2" DEEP)�
4 GANG RAISED COVER (1/2" or 3/4" DEPTH)
RAISED COVER�
MOUNTING SCREW�
(4 PLACES)
DIMENSIONS MULTIZONE�
CONTROLLER / DIMMER
FRONT DOOR�
COVER
OVERLAY
CONTRAST�
ADJUSTMENT�
(under Overlay)
CAUTIONS
CAUTIONS
• To be installed only by a qualifi ed Electrician
• Rated for indoor use only
• To be installed and/or used in accorance with appropriate electrical codes and regulations.
• If you are not sure about any part of these instructions, consult a qualifi ed electrician and Levi-
ton Tech Support at (800)959-6004.
• DO NOT connect line voltage wires to low voltage terminals. Product destruction in this manner
voids the warranty.
• To reduce the risk of over-heating and possible damage to this device and other connected
equipment, do not allow the connection of any portable device or for connections to a wall recep-
tacle.
• Do not connect to any unsupported load type (see device specifi cations).
• ALWAYS disconnect power when servicing this or any electrical device.
• All magnetic low voltage transformers should incoprorate a thermal cut-out or fuse on the pri-
mary windings in case of over-heating or failure.
• All fl uorescent lighting fi xtures must be grounded
• For use with copper wire only
• DO NOT mix load types on a single zone (ie: Tungsten, Fluorescent, Magnetic low voltage, etc.)
• Observe all lamp and fi xture manufacturer recommendations, warnings, and instructions.
WARNINGS
CAUTIONS
Power Calculation:
When using the D4006, D4104, D4206, or D4206 as a supply
to the Luma-Net network, ensure that there is enough supply
current.
AVAILABLE SUPPLY CURRENT:
+24Vdc, 300ma (12 Unit loads)
D4200 single gange devices each require 1 Unit Load
D4200 LCD stations each require 2 Unit Loads
Luma-Net hubs require 3 Unit Loads
When using Belden 1502R (or 1502P,) the following maxi-
mum run lengths apply:
Unit
Loads
Max run
length (ft)
10 3,528
20 1,764
30 1,176
40 882
Digital network termination:
The Luma-Net network requires that both ends of the net-
work be terminated:
For applications which
do not fi t these condi-
tions please contact the
factory for assistance.
NOTE:
When using low voltage wire with a rating
of less than 600V, insulate with the included
shrink tube sleeve.
Exploded Installation View
(beneath
Daisy Chain Toplogy:
Daisy-chain topology is required for each Luma-Net segment. Star or other similar
topologies are not allowed. If multiple home-runs are required, this topology can
be supported when a Luma-Net Hub, P/N LHUB8-000, is used.:
D4200 CONTROL STATION
PRESET SELECT STATION
C
12
18
15
16
17
13
14
6
9
10
11
7
8
3
4
5
1
2
A
B
DMX
CANCEL
LUMANET
CLEAR
PHASELOSS
AUXILIARY
FULLBRIGHT
COMMUNICATIONPORTS
FAN
SAVE
FULL
SELECT
BRIGHT
A2000-D
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DM
X
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
a-2000D
PRESET SELECT STATION
17
16
18
10
11
14
13
15
12
5
8
7
9
6
B
2
4
3
C
1
A
D4200 CONTROL STATION
LUMANET
DM
X
CLEAR
CANCEL
FAN
COMMUNICATION PORTS
FULL BRIGHT
AUXILIARY
PHASE LOSS
BRIGHT
SELECT
FULL
SAVE
LUMA-NET III HUB
BAD TOPOLOGY
(STAR)
GOOD TOPOLOGY
(HOME-RUN w/LUMA-NET HUB)
GOOD TOPOLOGY
(DAISY CHAIN)
Ground drain and shield
at only one end.
Common