Installation Manual

PK-A3226-10-00-0B
© 2018 Leviton Mfg. Co., Inc.
TRADEMARK DISCLAIMER
Use herein of third party trademarks, service marks,
trade names, brand names and/or product names are for
informational purposes only, are/may be the trademarks
of their respective owners; such use is not meant to
imply affiliation, sponsorship, or endorsement.
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
NOTE: All Leviton Disconnects are rated “Break all Lines” configurations and are suitable for motor circuits.
NOTE: Select conductor in accordance with ampacity of Table 310-15 of the National Electrical Code or Table 2 of the Canadian Electrical Code.
NOTE: Reference Table 3 for the recommended wire gauge for ampacity compliance with NEC
®
.
NOTE: For bending radius refer to specific UL standard and NEC
®
article.
NOTE: DO NOT tin conductors.
Cover Screws Tools
(Only one tool shown below required)
LDS30-FAX
LDS60-FAX
Flat head screwdriver wider than 1/4”, Phillips #3,
Robertson #3
LDS10-FAX Flat head screwdriver, Phillips #2
Table 1 - Tools for opening cover
* - Wire types TW, UF
**- Wire types RHW,THHW,THW,THWN,XHHW,USE,ZW, TBS, SA,SIS, FEP,FEPB, MI,RHH, RHW-2,THHN, THHW,THW-2,
THWN-2,USE-2, XHH, XHHW, XHHW-2, ZW-2
***- NEC table 250.122 for unit rated ampacities. For other types/styles refer to NEC.
Table 3 - Wiring Size
Model Rated
Current
UL Rating Min. Wire (AWG) copper conductors to meet
NEC table 310-15
(Phase and Neutral Wires)
Min. Wire (AWG)
copper conductors to
meet protective earth
requirements***
(60°C) Wire (AWG)*
( >75°C) Wire (AWG)**
LDS30-FAX 30A UL 98 #10 #10 #10
LDS60-FAX 60A UL 98 N/A #6 #10
LDS10-FAX 100A UL 98 N/A #3 #8
Model Switch Neutral Protective Earth Shield Ground
Terminal Terminal Terminal Terminal
AWG Strip length AWG Strip length AWG Strip length AWG Strip length
LDS30-FAX #14-8 0.5"(12mm) #24-8 0.4"(10mm) #26-8 0.4"(10mm) #24-12 0.3"(7mm)
LDS60-FAX #14-00(2/0) 0.5"(12mm) #16-1/0 0.7"(18mm) #16-2 0.7"(18mm) #24-8 0.4"(10mm)
LDS10-FAX #14-00(2/0) 0.7"(18mm) #16-2/0 0.9"(24mm) #16-2 0.7"(18mm) #20-6 0.4"(10mm)
Table 4 - Terminal Wiring Size & Strip Length
Model Switch Neutral Earth Shield Ground
LDS30-FAX 18 in-lbs (2 N-m) 15 in-lbs (1.7 N-m) 15 in-lbs (1.7 N-m) 5 in-lbs (0.6 N-m)
LDS60-FAX 35 in-lbs (4 N-m) 30 in-lbs (3.4 N-m) 30 in-lbs (3.4 N-m) 15 in-lbs (1.7 N-m)
LDS10-FAX 120 in-lbs (13.6 N-m) 60 in-lbs (6.8 N-m) 30 in-lbs (3.4 N-m) 15 in-lbs (1.7 N-m)
Table 5 - Terminal Screw Torque Ratings
Table 7 - Horsepower Ratings
LDS30-FAX LDS60-FAX LDS10-FAX
600 VAC 30 A 600 VAC 60 A 600 VAC 100 A
110 VAC 1ø 2 Hp 110 VAC 1ø 2 Hp 110-120 VAC 1ø 5 Hp
208-240 VAC 1ø 3 Hp 208-240 VAC 1ø 7.5 Hp 220-240 VAC 1ø 15 Hp
480 VAC 1ø 7.5 Hp 480 VAC 1ø 7.5 Hp 277 VAC 1ø 15 Hp
600 VAC 1ø 10 Hp 600 VAC 1ø 7.5 Hp 440-480 VAC 1ø 15 Hp
240 VAC 3ø 7.5 Hp 208-240 VAC 3ø 15 Hp 550-600 VAC 1ø 30 Hp
480 VAC 3ø 15 Hp 480 VAC 3ø 30 Hp 110-120 VAC 3ø 60 Hp
600 VAC 3ø 20 Hp 600 VAC 3ø 50 Hp 220-240 VAC 3ø 75 Hp
Table 6 - Cover Screw Torque Ratings
LDS30-FAX LDS60-FAX LDS10-FAX
18 in-lbs. (2 N-m) 18 in-lbs. (2 N-m) 18 in-lbs. (2 N-m)
Table 2 - Recommended conduit hub size & hole diameter
Model Fitting/Hub
(Trade size)
Hole Diameter Max Hub Size
LDS30-FAX* 3/4 in.** 1 in. (25.4 mm) 2” Trade Size
LDS60-FAX* 1-1/4 in.** 1.625 in. (41.3 mm) 2” Trade Size
LDS10-FAX* 1-1/4 in.** 1.625 in. (41.3 mm) 2” Trade Size
* NOTE: Refer to NEC Annex C for additional information.
** NOTE: Leviton provides hub grounding brackets for these sizes. All others use grounding hub.
30 Amp Fused Disconnect
110-277 VAC 1ø
30 Amp Fused Disconnect
Split Phase 120-240 VAC 1ø
30 Amp Fused Disconnect
208-600 VAC 1ø
30 Amp Fused Disconnect
208-600 VAC 3ø
30 Amp Fused Disconnect
208-600 VAC 3øY
60 Amp Fused Disconnect
110-277 VAC 1ø
60 Amp Fused Disconnect
Split Phase 120-240 VAC 1ø
60 Amp Fused Disconnect
208-600 VAC 1ø
60 Amp Fused Disconnect
208-600 VAC 3ø
60 Amp Fused Disconnect
208-600 VAC 3øY
100 Amp Fused Disconnect
110-277 VAC 1ø
100 Amp Fused Disconnect
Split Phase 120-240 VAC 1ø
100 Amp Fused Disconnect
208-600 VAC 1ø
100 Amp Fused Disconnect
208-600 VAC 3ø
100 Amp Fused Disconnect
208-600 VAC 3øY
a. Select wire gauge per Table 3. To ensure compliance with
UL/NEC wire bending space requirements, use wire sizes and
strip lengths per Table 4.
b. Tighten terminal screws per Table 5. c. Close cover and tighten cover screws per Table 6.
NOTE: Handle must be in the "OFF" position to install cover.
WARNING
: RISK OF ELECTRIC SHOCK. TURN OFF POWER
AT CIRCUIT BREAKER OR FUSE. DO NOT clean this product
while undergoing electrical maintenance or service.
CAUTION: Use only chemicals and cleaning solutions that
are safe for use with plastics and rubber gaskets.
CAUTION: DO NOT direct or concentrate high pressure water
or cleaning solution on the enclosure gasket seams, switch
handle area or exterior labels.
NOTE: Follow general cleaning procedures established by
your facility
NOTE: This product is certified by NSF
®
International to NSF/
ANSI/3-A 14159-1
DC <250 V 3-Pole DC <250 V 3-Pole
DIN RAIL
GROUND
TIE
GROUND
BUS
HUB
GROUNDING
PLATE
L1 L2 L3
T1 T2 T3
W
N
G
LOAD
G
G
DIN RAIL
GROUND
TIE
GROUND
BUS
HUB
GROUNDING
PLATE
L1 L2 L3
T1 T2 T3
W
N
G
LOAD
G
G
DC CONNECTION DIAGRAM
(DC RATED UNITS <250V, USE ALL POLES IN SERIES)
DIN RAIL
GROUND TIE
T1 T2 T3
L1 L2 L3
L
N
PE PE
N
GROUND BUS
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
T1 T2 T3
L1 L2 L3
L
L
TT
N
PE PE
N
GROUND BUS
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
T1 T2 T3
L1 L2 L3
L
L
PE PE
GROUND BUS
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
T1 T2 T3
L1 L2 L3
X
ZY
PE PE
GROUND BUS
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
T1 T2 T3
L1 L2 L3
X
ZY
W
PE PE
W
GROUND BUS
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
HUB GROUNDING PLATE
HUB GROUNDING PLATE
GROUND BUS
GROUND BUS
NEUTRAL BU
S
NEUTRAL BUS
PE N
N
G
NPE
NPE
T1 T2 T3
L1 L2 L3
L
NPE
NG
INTERNAL
LINK
DIN RAIL
GROUND TIE
GROUND BUS
GROUND BUS
NEUTRAL BU
S
NEUTRAL BUS
PE N
N
G
NPE
NPE
T1 T2 T3
L1 L2 L3
L L
NPE
NG
INTERNAL
LINK
HUB GROUNDING PLATE
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
GROUND BUS
GROUND BUS
NEUTRAL BU
S
NEUTRAL BUS
PE
N
G
PE
PE
T1 T2 T3
L1 L2 L3
L L
PE
NG
INTERNAL
LINK
HUB GROUNDING PLATE
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
GROUND BUS
GROUND BUS
NEUTRAL BU
S
NEUTRAL BUS
PE
N
G
PE
T1 T2 T3
L1 L2 L3
X Y Z
PE
NG
INTERNAL
LINK
HUB GROUNDING PLATE
HUB GROUNDING PLATE
DIN RAIL
GROUND TIE
GROUND BUS
GROUND BUS
NEUTRAL BU
S
NEUTRAL BUS
PE W
N
G
WPE
T1 T2 T3
L1 L2 L3
X Y Z
WPE
NG
INTERNAL
LINK
HUB GROUNDING PLATE
HUB GROUNDING PLATE
DIN RAIL
GROUND
TIE
GROUND
BUS
NEUTRAL
BUS
HUB GROUNDING PLATE
L1 L2 L3
T1 T2 T3
PE
L
N
PE N
N
G
HUB GROUNDING PLATE
DIN RAIL
GROUND
TIE
GROUND
BUS
NEUTRAL
BUS
HUB GROUNDING PLATE
L1 L2 L3
T1 T2 T3
PE
L L
N
PE N
N
G
HUB GROUNDING PLATE
DIN RAIL
GROUND
TIE
GROUND
BUS
NEUTRAL
BUS
HUB GROUNDING PLATE
L1 L2 L3
T1 T2 T3
PE
L L
PE
N
G
HUB GROUNDING PLATE
DIN RAIL
GROUND
TIE
GROUND
BUS
NEUTRAL
BUS
HUB GROUNDING PLATE
L1 L2 L3
T1 T2 T3
PE
X ZY
PE
N
G
HUB GROUNDING PLATE
DIN RAIL
GROUND
TIE
GROUND
BUS
NEUTRAL
BUS
HUB GROUNDING PLATE
L1 L2 L3
T1 T2 T3
PE
X ZY
W
PE W
N
G
HUB GROUNDING PLATE
CAUTION: Ampere rating of fuses must not exceed the maximum ampere rating of this device.
Continuous load current not to exceed 80% of the rating of fuses employed in other than motor
circuits. Refer to front cover for device’s maximum ampere rating.
Use UL “J” type or CSA HRC I-J listed; with ratings suitable for application. Common Industrial
suitable fuses for most applications are:
Cat. No. LDS30-FAX: Littelfuse JTD30 or Mersen AJT30.
Cat. No. LDS60-FAX: Littelfuse JTD60 or Mersen AJT60.
Cat. No. LDS10-FAX: Littelfuse JTD100 or Mersen AJT100.
Step 3: Wiring Tables
Cleaning Procedures
Statements
FOR CANADA ONLY
For warranty information and/or product returns, residents of
Canada should contact Leviton in writing at Leviton Manufacturing
of Canada Ltd to the attention of the Quality Assurance
Department, 165 Hymus Blvd, Pointe-Claire (Quebec),
Canada H9R 1E9 or by telephone at 1 800 405-5320.
a. Use hose directed water or cleaning solution to remove
any collected contaminants from behind the enclosure.
b. Use hose directed water or cleaning solution to remove
soil and contaminants from the exterior surfaces of the
enclosure.
c. Use a dry clean cloth to wipe away any excess water.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
LIMITED 3 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and
not for the benefit of anyone else that this product at the
time of its sale by Leviton is free of defects in materials
and workmanship under normal and proper use for three
years from the purchase date. Leviton’s only obligation
is to correct such defects by repair or replacement, at
its option. For details visit www.leviton.com or call
1-800-824-3005. This warranty excludes and there is
disclaimed liability for labor for removal of this product or
reinstallation. This warranty is void if this product is installed
improperly or in an improper environment, overloaded,
misused, opened, abused, or altered in any manner, or is not
used under normal operating conditions or not in accordance
with any labels or instructions. There are no other or implied
warranties of any kind, including merchantability and
fitness for a particular purpose, but if any implied warranty
is required by the applicable jurisdiction, the duration of any
such implied warranty, including merchantability and fitness
for a particular purpose, is limited to three years. Leviton is
not liable for incidental, indirect, special, or consequential
damages, including without limitation, damage to, or
loss of use of, any equipment, lost sales or profits or
delay or failure to perform this warranty obligation. The
remedies provided herein are the exclusive remedies under
this warranty, whether based on contract, tort or otherwise.
Fuses (not included)
WEB VERSION